1. Problem description & scope of application

This manual deals with the diagnosis and elimination of unintentional or intermittent false trips in safety-related control systems (SRP/CS) according to DIN EN ISO 13849-1 and DIN EN 62061. Such false trips, often referred to as “nuisance trips”, lead to unexpected machine downtimes, reduce system availability and can provoke inefficient or even dangerous workarounds by the operating personnel in order to maintain production. The primary causes often lie in the sensors, cabling, environmental influences or in the safety relay itself.

Affected system types include all machines and systems that have integrated safety functions, such as presses, robot cells, conveyor systems, packaging machines, automatic assembly machines and processing centers. The safety systems can include emergency stop devices, safety door monitoring, safety light barriers, laser scanners or two-hand controls. This manual aims to provide the maintenance technician with a systematic methodology for identifying and correcting such causes of errors.

Disruption Severity: CRITICAL

  • Unplanned production downtimes and significant costs.
  • Danger to operating personnel due to potential bypassing of safety devices.
  • Increased wear on machine components due to abrupt stops.

2. Safety instructions

IMPORTANT: Danger to life caused by electrical energy, mechanical movement and stored energy!

Before starting any diagnostic or maintenance work, the following measures must be strictly adhered to:

  • ENERGY SAFETY (LOTO): The entire system must be safely isolated from all energy sources in accordance with DIN EN ISO 14118 (avoiding unexpected startup), secured against being switched on again and checked for the absence of voltage. This includes electrical, hydraulic, pneumatic and mechanical energy.
  • Personal protective equipment (PPE): Always wear suitable PPE: safety glasses (DIN EN 166), safety shoes (DIN EN ISO 20345), protective gloves (DIN EN 388), if necessary hearing protection (DIN EN 352) and arc protection when working on control cabinets.
  • Residual energy: After the energy has been switched off, pay attention to stored energy (e.g. springs, capacitors, lifted loads, compressed air in accumulators). This must be dismantled or secured in a controlled manner before work on the machine begins.
  • Dangerous areas: Only authorized personnel are allowed to stay in the work area. Mark the area accordingly.
  • Comply with the manufacturer's instructions: Always follow the specific safety instructions of the machine and component manufacturer.

3. Required diagnostic tools

The correct equipment is crucial for efficient and precise fault diagnosis. The following tools are essential for troubleshooting security malfunctions:

Tool / device Specification/Model Measuring range / function Purpose
Digital multimeter (DMM) Fluke 87V, Metrawatt MetraHit Ultra VAC (0-1000V), VDC (0-1000V), Ω (0-50 MΩ), continuity, mA (0-10A) Voltage, current, resistance and continuity testing of cables and components.
Safety relay diagnostic tool Pilz PITestop, Siemens SIRIUS Safety ES, Rockwell Guardmaster Specific manufacturer software/hardware Functional test, reading out error codes and diagnostic messages of the safety relay.
Laser alignment device SICK, Keyence, Leuze Precision +/- 0.1mm Exact alignment of safety light barriers and optical sensors.
Thermography camera FLIR E-Series, Testo 872 -20°C to +650°C, thermal sensitivity < 0.05°C Identification of overheating on terminals, cables or components (loose connections, increased contact resistance).
Digital storage oscilloscope (DSO) Fluke ScopeMeter 190 Series, PicoScope 2000 Series 20MHz - 100MHz bandwidth, 100MS/s - 1GS/s sampling rate Analysis of signal integrity, noise, crosstalk and electromagnetic interference (EMI).
Cable testing and locating device Fluke IntelliTone, Megger MIT series Continuity, isolation (up to 1000V), cable length Localization of cable breaks, short circuits or poor insulation in the cabling.
Vibration meter SKF Microlog, PCE-VM 21 Acceleration (g), speed (mm/s), distance (µm) Detection of mechanical vibrations that could affect sensors or damage cables.
Pressure gauge (manometer) WIKA, Festo 0 – 16 bar, accuracy class 1.0 Checking pressure safety circuits in pneumatic or hydraulic systems.

4. Checklist for initial assessment

Before systematic diagnosis begins, a thorough initial assessment of the situation and machine status is crucial. This information helps narrow down the error context and avoid unnecessary steps.

aspect Observation/recording Purpose
Operating status at the time of the fault
  • Which machine/system part was affected?
  • Which operating mode was active (automatic, manual, setup)?
  • What actions were taken immediately before the trigger?
  • Were there people near the security device?
Isolate the error to specific operations or areas.
Current status of the safety device
  • Is a status LED on the sensor or relay lit?
  • Display on HMI/control panel?
  • Acoustic signals?
First indications of the type of error (e.g. signal path interrupted, relay error).
Alarms and error messages
  • Exact error message on HMI/control (PLC)?
  • Read out the error log of the PLC/IPC.
  • Timestamp of errors.
Detailed information about the source of the error and when it was triggered.
Recent changes
  • Have maintenance work, modifications or program updates been carried out?
  • Have components been replaced or readjusted?
  • Have new devices or machines been put into operation (potential EMI sources)?
Identification of potential causal relationships through changes.
Ambient Conditions
  • Any abnormalities in the environment (dust, humidity, oil, temperature, vibrations)?
  • Strong light sources (direct sunlight, headlights) near optical sensors?
  • Is there welding work or electric motors nearby?
Indications of external influences that may impair function.
Visual inspection
  • Damage to cables, plugs, sensors or protective devices?
  • Dirt on optical surfaces?
  • Loose terminals or corroded contacts?
Quickly identify obvious mechanical or electrical damage.

5. Systematic diagnostic flowchart for false trips

This decision tree guides the technician through a structured error analysis. Start by identifying the symptom and follow the instructions. Always remember the safety instructions in Chapter 2 before carrying out any work on the machine!

  1. Symptom: Machine stops unexpectedly, safety function triggered
    1. Is the triggering repeatable / reproducible?
      1. YES - error is reproducible:
        1. Is the error limited to a specific safety circuit or sensor?
          1. YES:
            1. Checking the affected safety circuit:
              • Safety light barrier / laser scanner:
                1. Visual inspection for contamination or damage to the optics.
                2. Check the transmitter-receiver axis with the laser alignment device (Chapter 3). Tolerance range: Max. 0.5 mm deviation at a distance of 5 m.
                3. Check the ambient light situation (direct sunlight, reflections).
                4. Check status LED on sensor (green: free, red: interrupted).
                5. IF Misalignment/Contamination: Clean and realign. → See Chapter 8.1.
              • Protective door safety switch / guard locking:
                1. Mechanical check of the door for play or jamming.
                2. Check actuator for damage or wear.
                3. Check electrical contacts of the switch for continuity using DMM (Chapter 3). Expected: < 0.5 ohms with closed contact, infinite with open.
                4. IF mechanical defect/contact error: Adjust or replace. → See Chapter 8.2.
              • Emergency stop button (E-Stop):
                1. Press the button manually and check for freedom of movement.
                2. Check electrical contacts for continuity with DMM. Expected: < 0.5 ohms when the contact is activated, infinite when the contact is at rest.
                3. IF button stuck/contact error: Replace. → See Chapter 8.3.
          2. NO - Error not limited to specific circuit / occurs on different circuits:
            1. Checking the central safety logic (safety relay / safety PLC):
              • Read out the error code on the safety relay or via diagnostic software (Chapter 3).
              • Check the voltage supply of the safety relay with DMM. Setpoint: 24 VDC +/- 5%.
              • Check reset function.
              • IF relay error code / voltage deviation: Replace relay / check voltage supply. → See Chapter 8.4.
      2. NO - Error occurs intermittently / is difficult to reproduce:
        1. Check cabling and EMC interference:
          1. Visual inspection of the entire cabling: For mechanical damage (kinks, chafe marks), loose wire end sleeves or corrosion.
          2. Use DMM (Chapter 3):
            • Resistance measurement of the cables of the affected sensors/actuators. Expected: < 1 ohm per 10m cable.
            • Wiggle tests on connectors and terminals during continuity testing.
          3. Use an oscilloscope (Chapter 3):
            • Check the signal spectrum of the safety lines for noise and spikes. Expected: Clean square wave signals, no voltage drops > 1Vpp.
            • Identify possible sources of electromagnetic interference (EMI) (variable frequency drives, large motors, welding equipment).
          4. Use thermography camera (Chapter 3): Check for hot spots on terminals and plugs. Temperature deviations > 10°C from the ambient temperature are noticeable.
          5. IF Cable defect / EMI: Replace cable / take EMC measures. → See Chapter 8.5.

6. Error-cause matrix

This matrix presents the most common symptoms, their likely causes, recommended diagnostic tests, and the expected results that confirm a cause.

Symptom Probable causes (by frequency) Diagnostic test Expected result if cause is confirmed
Intermittent triggering of the safety function
  1. Sensor misalignment/contamination
  2. Loose wiring/poor contacts
  3. Electromagnetic Interference (EMI/RFI)
  4. Vibrations (mechanical)
  5. Defective safety relay / PLC module (internal error)
  • Laser alignment sensor / visual inspection optics
  • DMM: Resistance, Continuity (Wiggle Test)
  • Oscilloscope: Check signal shape, identify sources of interference
  • Vibration measurement on sensor/cable
  • Safety relay diagnostic tool / status LED
  • Alignment deviation > 0.5 mm, optics dirty
  • Resistance fluctuates > 1 ohm, continuity interrupted
  • Signal noise > 1 Vpp, spikes
  • Vibration speed > 4.5 mm/s (DIN ISO 20816-1, limit range III)
  • Error code, intermittent status LED switching
Permanent triggering after system start / reset
  1. Cut cable / short circuit
  2. Mechanically actuated/blocked sensor (e.g. emergency stop pressed)
  3. Defective sensor (internal error)
  4. Defective safety relay / PLC module (failure)
  5. Incorrect parameterization / software error
  • DMM: continuity, insulation resistance
  • Visual inspection of sensor/button
  • Sensor function test (replacement sensor)
  • Safety relay diagnostic tool / status LED
  • Software comparison / backup import
  • Continuity interrupted (> 1 kOhm), short circuit (< 0.1 Ohm)
  • Sensor mechanically blocked
  • No signal / wrong signal at the sensor output
  • Permanent error code, red status LED
  • Error identified in configuration
Trip for certain movements/load conditions
  1. Cable breakage in drag chains / moving parts
  2. Sensor misalignment due to mechanical deformation
  3. Contact problems on connectors under load
  4. Induced disturbances caused by large loads/motors
  • DMM: Continuity during movement (wobble test)
  • Observe laser alignment during movement
  • Thermography camera under load
  • Oscilloscope: signal monitoring under load
  • Passage interrupted during movement
  • Alignment deviation > 0.5 mm during movement
  • Hot spot (> 10°C difference) on plug connection
  • Signal noise / voltage drops under load

7. Cause analysis for main error patterns

A deep understanding of the causes is crucial to prevent errors from recurring and to increase system availability. The following sections explain the most common root causes for false triggering of security systems.

7.1 Sensor misalignment or contamination

  • Why it happens: Mechanical vibrations, minor collisions, improper assembly, normal aging of the machine (settlement), dust deposits, oil mist, splashes of coolants or cleaning agents on optical surfaces. With retro-reflective sensors, foreign bodies in the measuring field or changing surface properties of the object can also be a cause.
  • How to confirm: Use a laser alignment device (Chapter 3) to accurately check the sensor axis. The tolerances for optical safety sensors are often tight, typically < 0.5 mm at a distance of 5 meters. A thorough visual inspection of the optics for dirt, damage or scratches. Observing the sensor status LEDs when the beam is undisturbed and interrupted.
  • Damage if not rectified: Continuous production interruptions due to false triggering. Danger that operating personnel bypass the safety device in order to maintain production, which represents a high safety risk and violates DIN EN ISO 13849.

7.2 Problems with cabling or contacting

  • Why it happens: Mechanical stress (bending changes, tension), vibrations, improper installation (radius too tight, lack of strain relief), corrosion on terminals or connectors, faulty wire end sleeves (DIN 46228), overheating due to currents that are too high or loose contacts (increased contact resistance). This often results in intermittent errors that are difficult to locate.
  • How to confirm it: Resistance measurement with DMM (Chapter 3) of the affected lines, ideally during a simulated machine movement (shake test). Insulation resistance test according to VDE 0100-600. thermography camera (Chapter 3) to identify hot spots on terminals, fuses or connectors under load. Visually check for chafe marks, kinks or crushed cables.
  • Damage if not repaired: Danger of arcing or fire in the event of short circuits. Intermittent failures, which lead to high diagnostic effort and greatly reduced machine availability. In safety-relevant circuits, a sporadic loss of contact can undermine the safety function, even if this is often compensated for by redundancy in PLe Cat. 4 systems (DIN EN ISO 13849-1).

7.3 Electromagnetic Interference (EMI)

  • Why it happens: Interference of interference signals from neighboring frequency converters, switching power supplies, motors, welding machines or inadequately shielded cables (DIN EN 61000-5-2). Poor grounding practices (VDE 0100-410) or lack of equipotential bonding can increase the effects of EMI. Sensors and wires act as antennas and capture this interference, resulting in erroneous signals.
  • How to confirm: Use an oscilloscope (Chapter 3) to visualize the signal quality on the sensor lines. Observation of noise or voltage spikes that do not correspond to the target signal. Switching off potential sources of interference one by one to isolate the cause. Temporary shielding of cables or components.
  • Damage if not corrected: Sporadic, irregular false triggering that is extremely difficult to diagnose. Damage to sensitive electronic components over a long period of time. Permanent reduction in signal quality and thus the reliability of the safety function.

7.4 Defective safety relays or PLC safety modules

  • Why it happens: Internal electronic component errors (e.g. aging, overvoltage), faulty firmware, heat stress, or improper parameterization. An insufficient or fluctuating voltage supply can also lead to malfunctions.
  • How to confirm: Reading error codes through the diagnostic interface of the safety relay or safety PLC (Chapter 3). Observing the status and diagnostic LEDs on the module. Checking the supply voltage (24 VDC +/- 5%) with a DMM. Replacing the module with a known working part for testing purposes.
  • Damage if not repaired: Complete failure of the safety system, which leads to a permanent machine downtime. In rare cases, a defective relay can also undermine the safety function itself, although modern safety relays have redundant architectures (e.g. 2-channel) to prevent this (Performance Level e, Category 4 according to DIN EN ISO 13849-1).

8. Step-by-step troubleshooting procedures

The following instructions describe detailed steps to resolve the identified causes of the error. Safety is a top priority – ALWAYS follow LOTO procedures in Chapter 2 before performing any work on the machine!

8.1 Resolve sensor misalignment or contamination

  1. Ensure safety: Secure the machine according to LOTO (Chapter 2).
  2. Visual inspection: Check optical surfaces of the sensor and reflector (if present) for dirt, dust, oil, scratches or damage.
  3. Cleaning: Clean optical surfaces carefully with a lint-free cloth and a suitable cleaner (e.g. isopropanol, not an aggressive solvent!).
  4. Check alignment:
    • Precisely align the transmitter and receiver (or reflector) using a laser alignment device (Chapter 3).
    • An optimal orientation is where the status LEDs of both sensors (if present) show maximum signal strength (often a continuous green light).
    • Requirement: The deviation of the optical axis must be a maximum of 0.5 mm at a distance of 5 meters.
  5. Check fastening: Check fastening screws and brackets for tightness and tighten if necessary. Observe the tightening torques according to the manufacturer's instructions (often 2-5 Nm for M4/M5 screws).
  6. Functional test: After releasing the machine (cancel LOTO), test the function of the safety device several times.

8.2 Troubleshoot wiring or contact issues

  1. Ensure safety: Secure the machine according to LOTO (Chapter 2).
  2. Locate faulty location: Based on diagnosis (DMM, thermography, oscilloscope - Chapter 3).
  3. Cable replacement if damaged:
    • Completely replace damaged cable sections with cables with the same specification (cross section, shielding, number of cores, bending radius). For moving applications, use flexible drag chain cables that are designed for 10 million bending cycles.
    • IMPORTANT: Always install shielded cables in accordance with DIN EN 61000-5-2 with the shield connection correctly connected to avoid EMC problems.
  4. Repair contact points:
    • Loose terminal connections: Relieve the load on the wires, strip the insulation again, provide them with suitable, correctly crimped wire end sleeves (according to DIN 46228) and tighten the terminals with the torque specified by the manufacturer. Typical tightening torques: 0.5 Nm for small terminals, 0.8-1.2 Nm for larger ones.
    • Corroded contacts: If there are slight signs of corrosion, carefully clean the contacts. If there is severe corrosion, components must be replaced.
    • Plug connections: Check whether the plug connection is tight and the lock is intact. If necessary, clean or replace the plugs.
  5. Strain relief and bending radii: Make sure that all cables are correctly strain-relieved and that the permissible bending radii (according to the cable manufacturer's specifications) are adhered to, especially on moving machine parts.
  6. Functional test: After releasing the machine (cancel LOTO), test the function of the safety device under various movement and load conditions.

8.3 Troubleshooting EMI issues

  1. Ensure safety: Secure the machine in accordance with LOTO (Chapter 2) before working on electrical systems.
  2. Identify source of interference: Using an oscilloscope and systematically switching potential sources on/off (frequency converters, motors, welding machines).
  3. Optimize cable management:
    • Separation: Separate safety-relevant signal lines spatially from power lines and frequency converter cables. Minimum distance 20 cm, intersections at 90° angles.
    • Shielding: Replace unshielded signal cables with high-quality, shielded cables (e.g. LiYCY or Profibus cable). The shielding must be placed on both sides (control and sensor) over a large area and with low inductance on the potential equalization (VDE 0100-410).
    • Ferrite cores: Place ferrite cores around signal lines at critical points to attenuate high-frequency interference.
  4. Grounding and potential equalization:
    • Checking the grounding of control cabinets, machine frames and electronic components in accordance with VDE 0100-410.
    • Ensuring reliable, low-resistance equipotential bonding of all machine parts to minimize common mode interference. Resistance between grounded parts < 0.1 ohm.
  5. Interference filter: If necessary, integrate EMC filters (e.g. EN 61000-4-4 compliant) into the power supply of components susceptible to interference or at the output of frequency converters.
  6. Functional test: After releasing the machine, check the interference immunity under normal and, if necessary, simulated interference conditions (e.g. welding machine nearby).

8.4 Elimination of defects in safety relays or PLC modules

  1. Ensure safety: Secure the machine according to LOTO (Chapter 2).
  2. Read error code: Via the diagnostic interface of the module or the LEDs on the device.
  3. Check voltage supply: Use DMM to check the 24 VDC supply voltage directly at the module terminals. Setpoint: 24 VDC +/- 5% (22.8 VDC to 25.2 VDC).
  4. Replace module:
    • If an internal defect is confirmed, replace the safety relay or PLC module with an identical replacement part certified by the manufacturer (e.g. CE, TÜV Rheinland certified).
    • IMPORTANT: Do not use non-certified or incompatible modules!
    • The wiring must be carried out exactly according to the circuit diagram.
  5. Parameterization / programming: For programmable safety PLC modules, transfer and check the correct program or parameters via the manufacturer's software (Chapter 3). Ensure that the configuration corresponds to the Performance Level (PL) or Safety Integrity Level (SIL) of the machine (DIN EN ISO 13849-1, DIN EN 62061).
  6. Functional test: After releasing the machine, carry out a comprehensive functional and acceptance test of the entire safety circuit, ideally in accordance with the specifications of DIN EN ISO 13849-2.

9. Preventive measures against false triggering

Prevention is the key to increasing operational safety and reducing unplanned downtime. By implementing the following measures, many false activations of security systems can be avoided.

Error Cause (Root Cause) Prevention strategy Monitoring method Recommended interval
Sensor misalignment/contamination
  • Regular cleaning of the optical surfaces.
  • Mechanically robust mounting of the sensors, protection against vibrations.
  • Use of protective housings for sensors in harsh environments.
  • Visual inspection and cleaning as part of machine maintenance.
  • Regular alignment check with laser alignment device.
  • Continuous signal monitoring (e.g. via PLC diagnostics).
Weekly (cleaning), Monthly (visual inspection), Semi-annual (alignment), Annual (signal monitoring).
Problems with cabling/contacting
  • Use of high-quality, flexible (if necessary shielded) cables in drag chains.
  • Correct strain relief and compliance with bending radii.
  • Careful wiring and crimping of the wire end sleeves (DIN 46228).
  • Regularly check that the terminals and connectors are firmly seated.
  • Regular visual inspection of the cables for damage.
  • Thermographic scan of terminals and control cabinet during operation.
  • Resistance measurement if contact resistance is suspected.
Quarterly (visual inspection), annually (thermography), every 2-3 years (resistance measurement).
Electromagnetic Interference (EMI)
  • Spatial separation of power and signal lines.
  • Consistent use of shielded cables for signals (DIN EN 61000-5-2).
  • Professional grounding and potential equalization concept (VDE 0100-410).
  • Use of EMC filters on sources of interference (frequency converters).
  • Periodic inspection of the grounding system.
  • Oscilloscopic measurement of signal quality in critical areas.
  • EMC measurements for major renovations or new systems.
Annually (grounding), on suspicion (oscilloscope), on changes (EMC measurement).
Defective safety relays / PLC modules
  • Compliance with environmental conditions (temperature, humidity).
  • Stable and filtered power supply.
  • Regular checking of diagnostic messages.
  • Scheduled replacement according to manufacturer recommendations (service life).
  • Monitoring system logs for error messages.
  • Regular functional testing as part of the inspection.
  • Checking the operating voltage with DMM.
Monthly (protocols), semi-annually (functional test), annually (voltage), replacement after 8-12 years (depending on component).

10. Spare Parts & Components

Prompt availability of certified replacement parts is critical to minimizing downtime when troubleshooting security system errors. UNITEC-D offers a wide range of high-quality industrial components. The following tables show example components that often need to be replaced in the event of false triggering.

Part name Specification/Standard When to replace UNITEC-D category
Safety light curtain (transmitter/receiver) Type 4 (EN ISO 13849-1), PLe, SIL3, range 0-15m, protective field height according to application In the event of damage to the optics/housing, internal defect (error code), unreliable function after cleaning/alignment. Safety technology & sensors
Safety relay/safety PLC module PLe, Cat. 4 (EN ISO 13849-1), SIL3 (EN 62061), 2-channel, programmable or hard-wired depending on the application. If there is an internal defect (error code, status LEDs), supply voltage is OK, but no function. Achievement of the manufacturer's specified service life (MTBFd). Safety technology & control components
Emergency stop button EN ISO 13850, Pilz or Siemens standard, with positive opening (NC contacts), illuminated or unilluminated. In the event of mechanical clamping, damage to the mushroom head, internal contact failure, after vandalism. Switchgear & command transmitters
Protective door position switch (with guard locking) EN ISO 14119 (Type 2 or Type 4), PLe, SIL3, contact types (NC/NO), locking force > 1000N. In case of mechanical wear of the actuator or housing, contact problems, defect in the locking function. Safety technology & limit switches
Shielded control cable LiYCY or similar, PVC/PUR jacket, flexible, nominal voltage 300/500V, EMC compliant according to DIN EN 61000-5-2. In case of visible damage, breaks, poor insulation values, recurring contact problems. Cables & Wires
Ferrite cores Split ferrite, diameter and length suitable for the cable, impedance at 100MHz > 100 ohms. After successfully identifying EMI as the cause, especially when retrofitting. EMC components

Find these and many other high-quality spare parts in our UNITEC-D e-catalogue.

11. References

  • DIN EN ISO 13849-1: Safety of machines - Safety-related parts of controls - Part 1: General design principles.
  • DIN EN ISO 13849-2: Safety of machines - Safety-related parts of controls - Part 2: Validation.
  • DIN EN ISO 14118: Safety of machines – avoiding unexpected startups.
  • DIN EN ISO 13850: Safety of machines – emergency stop function – design principles.
  • DIN EN ISO 14119: Safety of machines - locking devices in conjunction with separating protective devices - design principles for selection and application.
  • DIN EN 62061: Safety of machines - Functional safety of safety-related electrical, electronic and programmable electronic control systems.
  • VDE 0100-410 (DIN VDE 0100-410): Setting up low-voltage systems - Part 4-41: Protective measures - Protection against electric shock.
  • DIN EN 61000-5-2: Electromagnetic Compatibility (EMC) – Part 5-2: Installation and Migration Guidelines – Grounding and Cabling.
  • Manufacturer documentation for specific safety products (e.g. Pilz, Siemens, SICK).