Maintenance instructions sewage treatment plant: aeration system, sludge pumps and pH control

Technical analysis: Wastewater treatment plant maintenance: aeration system inspection, sludge pump service, and pH cont

1. Scope and Purpose

This maintenance manual covers the three critical subsystems of industrial wastewater treatment plants as standard in manufacturing companies in the DACH region (automotive, chemical, food):

  • Ventilation system: Rotary lobe blower (15–75 kW), membrane aerator (fine/coarse bubble), air distribution lines DN80–DN300
  • Sludge pumps: Eccentric screw pumps and rotary lobe pumps for primary/surplus sludge (flow rate 5–80 m³/h)
  • pH value control: Inline pH probes, dosing pumps, calibration systems

Implementation times: Ventilation system every 2,000 operating hours or quarterly. Slurry pumps every 1,500 hours of operation. pH calibration weekly to fortnightly according to DIN 19268.

Normative bases: DIN EN 12255 (sewage treatment plants), DIN EN 12723 (pumps), VDI 2035 (water treatment), DIN 19268 (pH measurement), VDE 0100-710 (electrical systems in medically used areas - here analogous for moist/corrosive environments), ATEX Directive 2014/34/EU for explosive areas for digester gas.

2. Safety instructions

WARNING - LOCKOUT/TAGOUT (LoTo): Before any work on fans, pumps or electrical components, a complete isolation must be carried out in accordance with DIN EN ISO 14118. All energy sources (electrical, pneumatic, hydraulic) must be disconnected and secured against being switched on again.

WARNING - CHOKING HAZARD: In closed pools and shafts there is a risk of oxygen deficiency due to H₂S and CH₄. Before entering: Carry out a gas measurement (O₂ > 19.5% vol., H₂S < 5 ppm, CH₄ < 10% LEL). Release certificate required according to DGUV Rule 113-004.

WARNING — BIOLOGICAL HAZARD: Wastewater contains pathogenic germs. Avoid skin contact. Disinfect immediately after contact. Hepatitis A vaccination recommended for maintenance personnel.

WARNING — ATEX ZONE: ATEX zones 1/2 apply in the area of ​​digestion towers and closed sludge collectors. Only use approved tools and measuring devices (ex protection category II 2G).

Required PPE

  • Chemical Resistant Gloves (EN 374, Type A)
  • Safety glasses with side protection (EN 166)
  • Safety shoes S5 (EN ISO 20345) — waterproof, puncture-proof
  • Disposable protective suit type 4/5 (EN 14605) for mud work
  • Respiratory protection: Half mask with ABEK filter when working in shafts, alternatively air-independent respiratory protection when driving
  • Gas detector 4-gas (O₂, H₂S, CH₄, CO) - calibrated, test < 6 months old

3. Tools and materials

Tool/MaterialSpecificationnumber
Torque wrench10–50 Nm, ratchet 3/8"1
Torque wrench40–200 Nm, ratchet 1/2"1
multimeterTrue RMS, CAT III 600V, insulation measurement ≥ 500 V DC1
Vibration meterFrequency range 10-1000 Hz, resolution 0.01 mm/s1
Infrared thermometerRange -30 to +500 °C, emissivity adjustable1
Pressure gauge0–1 bar, accuracy ±0.5%, connection G1/4"2
pH calibration solutionspH 4.01 / pH 7.00 / pH 10.01 (DIN 19266, traceable)250 ml each
Stator lubricantFood-grade lubricant (NSF H1) for progressive cavity pumps1 tube 400 ml
Membrane diffuser seal setEPDM, Ø depending on the aerator type10 pcs. reserve
flange gasketsEPDM, DN80–DN150, PN10/162 each
Gas detector4-Gas (O₂/H₂S/CH₄/CO), ATEX II 1G1
Feeler gauge0.02-1.00mm, 20 sheets1 sentence
StrobeFlash frequency 60-99,999 FPM1
Cable lugs/toolsCrimping pliers 0.5-6 mm², insulated cable lugs1 set

4. Pre-maintenance inspection checklist

No.CheckpointExamAcceptance criterionRemark
4.1LoTo statusVisual control of all separation pointsAll switches open, locks in place, zero voltage test confirmedSign the protocol
4.2Gas free measurement (during shaft work)4-gas measurement at working depthO₂ 19.5-23%, H₂S < 5 ppm, CH₄ < 10% LEL, CO < 30 ppmRepeat every 30 minutes
4.3Fan housing temperatureIR thermometer on pressure side≤ 120 °C (rotary blower), ≤ 80 °C (side channel blower)Exceedance → Clarify cause before maintenance
4.4Fan vibration levelRadial vibration measurement on the bearing housing≤ 4.5 mm/s (ISO 10816-3, group 2)If > 7.1 mm/s: immediate action
4.5Slurry pump leakageVisual inspection of shaft sealNo visible leakage, maximum moisture filmDripping seal → plan replacement
4.6Pressure loss ventilation networkPressure gauge before/after distributorDifferential pressure ≤ 50 mbar at nominal air volumeHigher value → constipation likely
4.7pH probe conditionVisual inspection of the glass electrodeNo cracks, no deposits on the diaphragm, electrolyte level OKReplace broken probe immediately
4.8Electrical connectionsVisual inspection of terminals, cable entriesNo corrosion, no loose terminals, IP protection intactReplace corroded terminals

5. Step-by-step procedure

5.1 Ventilation system — inspection and maintenance

  1. Disconnect the fan electrically. Main switch to OFF, attach LoTo lock. Perform a zero voltage test on the multimeter (AC V, range 0-600 V). Release residual pressure via vent valve (target pressure: 0 bar overpressure).

    Common mistake: Forgetting the pneumatic residual pressure in the pressure line. Always read the pressure gauge before loosening flanges.

  2. Check and clean the intake filter. Open the filter housing (4× M8 screws, torque when reinstalling: 15 Nm). Remove filter element. Document differential pressure during operation (acceptance: ≤ 25 mbar clean, change at ≥ 50 mbar). Blow out or replace the filter element with compressed air (max. 3 bar, nozzle distance ≥ 150 mm) from the inside to the outside.

    Visual indicator: Filter material evenly bright, no oil stains, no cracks.

  3. Check V-belt/belt drive (if present). Check belt tension: Depth of indentation at 10 N force = 3–5 mm per 100 mm free span length. Check wear markers on belt flanks. Belt alignment with laser alignment device (tolerance: ≤ 0.5°/0.5 mm parallel offset).

    Common error: Excessive belt tension leads to bearing damage on the fan. Observe manufacturer's instructions.

  4. Document the bearing temperature and vibration. Measure IR thermometers at both bearing locations. Acceptance: Storage temperature ≤ 80 °C (ambient + 40 K). Radial and axial vibration measurement on each bearing. Enter values ​​in trend map.

  5. Check the membrane aerator in the pool. Partially empty the pool (if possible) or use a diver/camera. Observe the aerator pattern when the fan is running: Uniform bubble formation over the entire pool surface. Individual “dead

Related Articles