1. Description of the Problem and Scope of Application
This manual is intended for diagnosing and troubleshooting electrical panel overheating in industrial environments. Overheating of electrical switchboards, motor control cabinets, automation panels and other electrical components is a critical indicator of potential equipment failures, reduced efficiency, reduced component life, and a serious fire and personnel safety threat. It can lead to unplanned production stoppages, significant financial losses and damage to expensive equipment.
This guide covers overheating of the following types of equipment:
- Distribution panels (PS)
- Motor control cabinets (SHD)
- Automation and process control panels
- Uninterruptible power supply systems (UPS)
- Transformer substations (low-voltage parts)
Severity Classification:
- Critical: The temperature of the components exceeds the maximum allowable values set by the manufacturer (for example, +80°C for copper busbars or +60°C for circuit breaker housings), or there is intense sparking, smoke, burning smell. Immediate shutdown and fault localization are mandatory.
- Significant: Component temperature exceeds normal operating values by +20°C or more (eg ΔT > 20°C relative to adjacent elements or ambient temperature), but does not reach critical. Requires urgent intervention.
- Minor: Temperature of components is 5-15°C higher than normal operating values. Requires scheduled diagnostics and elimination during the next maintenance.
2. Precautions
CAUTION! High Voltage and Arc Discharge!
- Lockout and Tagout (LOTO): Before any work with opening panels, checking connections or replacing components MANDATORY de-energize the relevant circuit and apply Lockout/Tagout procedures in accordance with internal safety regulations and DSTU EN 50110-1:2017. Check the absence of voltage with the indicator.
- Personal Protective Equipment (PPE): When performing diagnostic work, especially during thermography or measurements under voltage, MANDATORY use appropriate PPE: dielectric gloves (class 00, 0, 1 or 2 depending on the voltage), safety glasses or a face shield, flame-resistant clothing (arc-rated protection category according to NFPA 70E), dielectric footwear.
- Stored Energy: Capacitors can store a dangerous charge even after the power is turned off. CAUTION discharge them before starting work or wait enough time for self-discharge.
- Work under voltage: Work under voltage is extremely dangerous and is allowed only by qualified personnel with the appropriate permit and PPE, with strict adherence to technological maps and minimum safe distances according to DSTU EN 50110-1:2017.
- Working Area: Provide free access to the panel, exclude the presence of outsiders. Use warning signs and fences.
3. Necessary Diagnostic Tools
The following list of tools is required for effective and safe diagnosis of overheating of electrical panels:
| Name of the Tool | Specification/Model | Measurement range | Purpose |
|---|---|---|---|
| Thermal imager (thermographic camera) | Flir T-Series / Testo 8xx | -20°C to +650°C, sensitivity < 0.03°C @ 30°C | Visualization of temperature fields, quick detection of hot spots and overheating zones by non-contact method. Critical for initial diagnosis. |
| Digital Multimeter (True-RMS) | Fluke 179 / Testo 760-3 | U: up to 1000V AC/DC; I: up to 10A AC/DC; R: up to 50 MΩ | Measurement of voltage, current (indirectly), resistance, checking the integrity of circuits and voltage drop at connections. |
| Current Clamps (True-RMS) | Fluke 376 FC / Testo 770-3 | I: up to 1000A AC/DC; U: up to 1000V AC/DC | Non-contact measurement of current in conductors, measurement of starting currents, measurement of voltage and resistance. True-RMS is required for accurate readings with non-sinusoidal currents. |
| Power Quality Analyzer | Fluke 435 Series II / Chauvin Arnoux Qualistar+ | U: up to 1000V; I: up to 6000A; F: up to 400 Hz; Harmonic distortion coefficient (THD), individual harmonics up to the 50th. | Measurement and analysis of harmonic distortion (THD), phase distortion, power factor, power (P, Q, S). Critical for detecting harmonic and load problems. |
| Pyrometer (IR-Thermometer) | Raytek MiniTemp MT4 / Testo 830-T2 | -30°C to +500°C, accuracy ±1.5°C | Quick point measurement of the temperature of surfaces to confirm the readings of the thermal imager or in its absence. |
| Set of Isolated Screwdrivers | Wera Kraftform VDE / Wiha SlimFix VDE | Up to 1000V AC, standards EN 60900 / DSTU EN 60900 | Safe operation with connections under potential voltage (after de-energization and inspection). |
| Torque Wrench / Screwdriver | Wera Torque VDE / Gedore Torque | Range 0.5 – 25 Nm (depends on the model) | Ensuring correct torque of electrical connections in accordance with manufacturer's recommendations and industry standards. |
4. Initial Evaluation Checklist
Before starting a detailed diagnosis it is critically important to gather as much information as possible about the operating conditions and history of the malfunction. This will help narrow down the range of possible causes.
| Points Rating | Details for Observation/Recording | Remarks |
|---|---|---|
| Visual Panel Overview |
|
Pay attention to any unusual signs. |
| The smell |
|
A strong odor may indicate smoldering or overheating. |
| sounds |
|
May indicate weak connections or arc discharge. |
| Ambient Temperature |
|
High ambient temperatures can make the problem worse. |
| Terms of Use |
|
It is important to assess the thermal regime. |
| Accident and Service History |
|
Helps identify recurring faults. |
| Indications of Measuring Devices |
|
Primary data for analysis. |
| Pollution |
|
Contamination prevents heat dissipation. |
5. Systematic Diagnostic Algorithm
This algorithm is designed to systematically identify the root cause of overheating of an electrical panel. Follow the sequence of steps.
- Initial Assessment and Thermographic Survey
- IF overheating of the electrical panel is observed (visually, by touch, activation of the thermal relay).
- THEN complete the initial evaluation checklist (section 4).
- THEN perform a thermographic survey (use a thermal imager, section 3). WARNING: perform under voltage, observing all safety precautions and using appropriate PPE!
- Setting the thermal imager: Set the Emissivity coefficient according to the surface material (for example, 0.95 for painted metal surfaces, 0.7-0.8 for oxidized copper busbars, 0.98 for insulation). The distance to the object and the viewing angle should be optimal to avoid distortions.
- IF thermography reveals a localized hot spot (ΔT > 20°C relative to surrounding components):
- THEN proceed to diagnosis of weak connections and component faults (Step 2).
- IF thermography detects general overheating of the panel (uniform temperature increase throughout the volume):
- THEN go to diagnosis of overload and harmonic distortion (Step 3).
- IF thermography shows increased temperature, but no obvious hot spots or general overheating:
- THEN proceed to diagnosing ventilation and cooling problems (Step 4).
- IF overheating of the electrical panel is observed (visually, by touch, activation of the thermal relay).
- Poor Connections and Component Fault Diagnosis (for localized overheating)
- IF a hot spot is detected on terminal connections, buses, contactors, circuit breakers or relays:
- THEN perform the LOTO procedure (Section 2).
- THEN visually examine the hot spot: look for traces of burning, oxidation, deformation.
- THEN check the tightening torque of the screw connections using a torque wrench/screwdriver. Norm: according to EN 60947-1 / DSTU EN 60947-1:2017, or the recommendations of the component manufacturer (usually 1.5-20 Nm depending on the conductor cross-section).
- THEN using a multimeter (in resistance measurement mode, after turning off the power), measure the resistance at the connection point. Norm: resistance should be close to 0 ohms (tens of microohms). IF resistance is higher than 0.01 Ohm, this indicates a bad contact.
- THEN with the help of a multimeter (in voltage measurement mode, under nominal load) measure the voltage drop on the hot connection. Norm: voltage drop should not exceed 50 mV. IF drop > 50 mV, this indicates a weak contact.
- IF the fault is localized on a specific component (contactor, relay, circuit breaker):
- THEN check its operability, perform functional testing (for example, check contactor contact operation, check circuit breaker thermal settings).
- THEN compare the measured current through the component (current clamps, section 3) with its rated current. IF current is close to rated and the component overheats, THEN its internal fault is likely.
- IF a hot spot is detected on terminal connections, buses, contactors, circuit breakers or relays:
- Diagnostics of Overload and Harmonic Distortions (for general overheating)
- Measurement of Currents and Loads:
- THEN with the help of current clamps (True-RMS, section 3) measure the currents in all phases of the input power of the panel and on all its output lines.
- THEN compare the measured currents with the rated values of the circuit breakers, cables and busbars. IF the measured current exceeds 80% of the rated current, THEN there is a possibility of overload.
- THEN check phase skew by current. Norm: no more than 10% difference between phases (according to DSTU EN 50160). IF skew > 10%, THEN it can cause overheating of one of the phases.
- IF an overload is detected on one or more lines/phases:
- THEN proceed to overload troubleshooting (Chapter 8).
- Analysis of Harmonic Distortions:
- THEN using the power quality analyzer (chapter 3), measure the harmonic distortion coefficient (THD) and the spectrum of individual harmonics (up to the 50th) in terms of current and voltage.
- Norm: The total current harmonic distortion coefficient (THDi) for individual consumers according to EN 61000-3-2/3 should not exceed 5-10% depending on the type of load and power supply system. By voltage (THDu) according to DSTU EN 50160:2017 – usually no more than 8% for a 0.4 kV system.
- IF THDi > 10% or significant amplitudes of the 3rd, 5th, 7th harmonics are observed:
- THEN proceed to solving the problem of harmonic distortions (Chapter 8).
- Measurement of Currents and Loads:
- Diagnosis of Ventilation and Cooling Problems (for general minor overheating)
- THEN perform a visual inspection of the panel ventilation system:
- Check the cleanliness of ventilation grids, filters.
- Check the efficiency of the fans (if installed), their rotation, noise level.
- Check the tightness of the panel, whether there are any unauthorized holes that disturb the air flow.
- THEN measure the temperature inside the panel and near the inlet/outlet vents using a pyrometer. IF the temperature difference is significant (ΔT > 10°C), THEN the cooling system works inefficiently.
- IF detected clogging, malfunctioning fans, or insufficient air circulation:
- THEN proceed to ventilation and cooling problems (Chapter 8).
- IF all of the above checks have found no obvious cause and overheating persists, THEN consider the possibility of insulation degradation or hidden internal component defects requiring more in-depth diagnosis or replacement.
- THEN perform a visual inspection of the panel ventilation system:
6. Malfunction-Cause matrix
This chart will help you quickly identify likely causes of overheating based on observed symptoms and diagnostic test results.
| Symptom | Probable Causes (ranked by probability) | Diagnostic Test | Expected Result if Cause Confirmed |
|---|---|---|---|
| Localized overheating (hot spot) at connection/terminal. | 1. Weak/poor connection (oxidation, insufficient tightening torque). 2. Overloading of a separate branch/conductor. 3. Degradation of conductor/terminal material. |
Thermography, measuring the voltage drop (under load) at the connection, checking the tightening torque. | ΔT > 20°C (thermography), voltage drop > 50 mV, loose connection. |
| Localized component overheating (automatic machine, contactor, relay). | 1. Component overload. 2. Internal malfunction/wear of the component (burning of contacts, loosening of springs). 3. Incorrectly selected component (insufficient nominal value). |
Thermography, measurement of current through the component, functional verification, visual inspection of contacts (after LOTO). | ΔT > 20°C (thermography), the measured current is close to or exceeds the component rating. |
| General overheating of the panel (evenly over the entire volume). | 1. General panel overload. 2. Significant harmonic distortions in the system. 3. Insufficient or ineffective ventilation/cooling system. 4. High ambient temperature. |
Measurement of currents of input lines, analysis of power quality (THD), verification of ventilation, measurement of ambient temperature. | Currents > 80% of cables/buses rating, THDi > 10%, blocked filters, non-working fans, room temperature > +35°C. |
| Overheating of the neutral conductor without visible phase overload. | 1. Presence of asymmetric nonlinear loads (PC, UPS, LED lighting) generating the 3rd harmonic and its multiples. 2. Phase shift. |
Analysis of the quality of electricity (spectrum of harmonics, THDi), measurement of the current in the neutral. | Significant current in the neutral (may exceed the phase current) with insignificant phase currents, high content of the 3rd harmonic. |
| The panel overheats only when certain equipment is activated. | 1. The connected load exceeds the calculated one. 2. The component that controls this equipment (contactor, relay) is faulty. |
Current measurement during activation of the equipment, thermography of the control component. | Current > nominal, localized overheating of the control component. |
7. Root Cause Analysis for Each Malfunction
7.1. Loose or Poor Electrical Connections
Why this happens: Over time, electrical connections can weaken due to vibration, thermal expansion and contraction, improper installation torque, or oxidation of contact surfaces. According to EN 61439-1 / DSTU EN 61439-1:2017, the correct connection should provide minimum transient resistance. If the contact resistance increases, even a small current leads to a significant release of heat according to the Joule-Lenz law (Q = I² * R). This leads to local overheating.
How to confirm:
- Thermography: The most effective method. Detects hot spots with ΔT > 20°C.
- Measure the voltage drop: Using a multimeter, measure the voltage drop across the connection under a working load. A drop of more than 50 mV indicates a poor contact.
- Visual inspection: Traces of oxidation, burning, discoloration of the insulation, darkening of the metal at the joint.
What damage does this cause if left unaddressed: Continued overheating will degrade the insulation, which can cause a short circuit or phase-to-phase fault. Complete destruction of the connection, failure of powered equipment, and the occurrence of a fire are possible. According to the requirements of UkrSEPRO, such equipment is considered dangerous.
7.2. Overloading of Electrical Rings or Components
Why it happens: An overload occurs when the current flowing through a conductor, device or cable exceeds its rated (permissible continuous) current. This can be the result of new equipment being connected without proper load calculations, connected devices malfunctioning (eg motor jamming resulting in increased current), or improper system design. According to EN 60364 / DSTU 4831:2007 (Electrical installations of buildings), overloading is unacceptable.
How to confirm:
- Current measurement: Use a current clamp (True-RMS) to measure the current in all phases. Compare the measured values with the rated values of the circuit breakers, cables and components. IF current exceeds 80% of nominal, THEN it is a potential overload.
- Load graph analysis: Using a power quality analyzer for long-term current and power monitoring.
What damage does it cause if left unaddressed: Prolonged overload causes accelerated aging of insulation, reduced life of cables and protection devices. This can lead to the activation of protection (knockout of automatic devices), damage to conductors, and in critical cases - to ignition. Possible damage to powered equipment due to voltage drop.
7.3. Harmonic Distortions
Why this happens: Harmonics are currents or voltages that have frequencies that are multiples of the mains frequency (eg 150 Hz for the 3rd harmonic on a 50 Hz network). They are generated by non-linear loads, such as inverters, frequency converters, pulsed power supplies (computers, LED lighting), welding machines. Harmonics do not generate useful power, but cause additional heating of conductors, transformers and capacitors due to the increase in the rms value of the current and the skin effect. Particularly dangerous is the 3rd harmonic, which in three-phase systems is not compensated and accumulates in the neutral conductor, causing it to overheat.
How to confirm:
- Power quality analyzer: Measurement of total harmonic distortion (THD) and spectrum analysis of individual harmonics by current (THDi) and voltage (THDu). IF THDi > 10% (according to EN 61000-2-4), THEN harmonics are a significant problem.
- Measurement of the current in the neutral: High current in the neutral with a balanced phase load is a clear indicator of the presence of the 3rd harmonic.
The damage it causes if left unaddressed:Additional heating of cables, transformers, capacitors and circuit breakers, which can cause them to fail prematurely. Reduction of equipment efficiency. False activation of protective devices is possible. Overheating of the neutral conductor can cause fire.
7.4. Malfunctions of Internal Components
Why this happens: Individual components inside the panel (for example, circuit breakers, contactors, relays, current transformers) can fail due to age, a factory defect, mechanical wear of contacts, exposure to aggressive environments or exceeding permissible loads. The internal resistance of such a component increases, which leads to its own overheating even at normal current.
How to confirm:
- Thermography: Localized overheating of a specific component.
- Functional testing: Check of operation, absence of backlash, integrity of the case.
- Resistance measurement: After de-energizing, measure the resistance across the component (e.g. through contactor contacts). High resistance indicates a malfunction.
What damage does it cause if left unaddressed: Reduced system reliability, unplanned shutdowns. Complete destruction of the component is possible with the formation of an arc discharge, which can damage neighboring elements or cause a fire.
7.5. Insufficient Ventilation and Pollution
Why this happens: Electric panels are designed for a certain heat output. If natural or forced ventilation is impaired (clogged filters, non-functioning fans, blocked openings), the heat generated by the components is not efficiently dissipated, resulting in an increase in the overall temperature inside the panel. Accumulations of dust, dirt and oil deposits act as a thermal insulator, impeding heat transfer and increasing the risk of short circuits.
How to confirm:
- Visual inspection: Clogged filters, dust on components, stationary fan blades.
- Temperature measurement: Temperature measurement inside the panel and near the vents.
What damage does it cause if left unaddressed: Accelerated aging of all panel components (cables, switches, electronic modules) due to constant exposure to elevated temperatures. Reducing their reliability and service life. Increased risk of failure and fire.
8. Step-by-Step Troubleshooting Procedures
8.1. Elimination of Weak Connections
CAUTION! Do the full LOTO procedure for the electrical panel in question. Check the absence of voltage using the indicator.
- Contact Cleaning: Remove oxidation, dirt, or corrosion from contact surfaces using special electrical contact cleaners (e.g., alcohol solutions, lint-free wipes). Avoid abrasive materials.
- Retightening Connections: Using a torque wrench/screwdriver, tighten all screw connections (terminal blocks, busbar bolts, wire fasteners to machines) to the torque recommended by the component manufacturer or according to the tables of standard tightening torques (for example, for copper wires 10 mm² - 4-5 Nm, for busbars - 10-20 Nm depending on the cross-section).
- Visual Check: Make sure the contact is secure, the wires and insulation are not deformed.
- Verification: After power is restored (with safety in mind), repeat the thermographic survey and voltage drop measurement on the repaired connection under working load. Expected result: ΔT < 5°C, voltage drop < 50 mV.
8.2. Solving Overload Problems
CAUTION! Do the full LOTO procedure for the electrical panel in question. Check the absence of voltage using the indicator.
- Identifying the Source of Overload: Analyze what equipment was connected or modified that caused the load to increase.
- Load Redistribution: If possible, redistribute part of the load to other, less loaded, electrical lines or panels. This requires careful design and testing of phase balance.
- Increasing the Cross Section of Cables/Bus: If redistribution is not possible, and the calculations show a constant excess of the permissible current, it is necessary to replace overloaded cables and/or buses with components with a larger cross section, capable of withstanding the new level of current (according to DSTU IEC 60364-5-52:2016).
- Replacement of Circuit Breakers: Replace overload-triggered circuit breakers with appropriately rated circuit breakers if the previous ones were improperly selected (but only after eliminating the root cause of the overload).
- Verification: After completing the work, re-measure the currents in all phases and lines using current clamps. Expected result: Currents should not exceed 80% of the rated current of cables and protection devices.
8.3. Elimination of Harmonic Distortions
- Identifying Harmonic Sources: Using a power quality analyzer, determine which loads generate the most harmonic distortion (usually variable speed drives, UPS, induction furnaces, computers).
- Installing Harmonic Filters:
- Passive filters: Installed in parallel or in series with the load to suppress certain harmonics (for example, LC filters for 3rd, 5th harmonics).
- Active filters: Dynamically generate anti-phase harmonics, compensating distortion in real time. More effective, but more expensive.
- System Configuration Change: If possible, separate non-linear loads from sensitive equipment. Using transformers with YNyn or Dyn11 wiring can help reduce the spread of harmonics.
- Increasing the Cross Section of the Neutral Conductor: If the main ones are the 3rd harmonics, which lead to overheating of the neutral, it may be necessary to increase the cross section of the neutral conductor to 1.73 - 2 times relative to the phase ones (according to EN 60364-5-52).
- Verification: Re-analysis of electricity quality after implementation of solutions. Expected result: Reduction of THDi to values < 10%, reduction of current in the neutral conductor.
8.4. Replacement of Faulty Components
CAUTION! Do the full LOTO procedure for the electrical panel in question. Check the absence of voltage using the indicator.
- Disassembly: Carefully disassemble the faulty component, following the manufacturer's instructions.
- Installation: Install a new component identical in type and nominal characteristics. Critical: use components that comply with CE, UkrSEPRO standards.
- Connection: Connect all wires following the diagram, using a torque wrench to tighten the connections to the recommended torque.
- Verification: After power is restored, perform functional testing of the new component as well as repeat thermographic examination. Expected result: Normal operation, no overheating.
8.5. Improved Ventilation and Cooling
CAUTION! Follow the full LOTO procedure if you need to open the panel to clean or replace fans. You may not need LOTO to clean the exterior grills, but keep a safe distance from live parts.
- Cleaning: Using compressed air (no metal particles), a brush and a vacuum cleaner, clean the ventilation grilles, air filters and the inner surfaces of the panel from dust and dirt. IMPORTANT: Ensure proper air filtration.
- Replacing Fans: If the fans do not work or work inefficiently, replace them with new ones with the appropriate performance characteristics and degree of IP protection.
- Installation of Additional Cooling Systems: If passive and forced ventilation cooling is not sufficient (for example, due to high density of components or ambient temperature > +40°C), consider installing air conditioners for electric cabinets or liquid cooling systems.
- Verification: Re-measurement of the temperature inside the panel and near the outlets. Expected result: Reduction of the temperature inside the panel to acceptable values (for example, ΔT < 15°C relative to the ambient temperature).
9. Preventive Measures
Regular preventive measures are key to prevent overheating of electrical panels and ensure smooth operation of the equipment.
| The root cause | Prevention Strategy | Monitoring method | Recommended Interval |
|---|---|---|---|
| Weak connections | Regular checking and tightening of terminal connections according to the recommended moments. Using special washers (eg Belleville) to maintain pressure. | Thermographic examination (EN 13187), measurement of voltage drop, checking of the tightening moment with a dynamometric tool. | Annually or every 6 months for critical equipment. |
| Overload | Careful calculation of loads during design and any modifications. Provision of sufficient current reserve for cables and protection devices (at least 20%). | Regular monitoring of currents and power (current clamps, power quality analyzers). Analysis of load schedules. | Monthly (for large consumers), annually (for the entire panel). |
| Harmonic distortions | Use of equipment with a low level of harmonics. Use of active or passive harmonic filters. | Regular analysis of power quality (THD, spectrum of harmonics) using specialized devices. | Annually or when connecting a new non-linear load. |
| Malfunctions of internal components | Scheduled replacement of components with a limited service life (for example, contactors with a large number of switches). Use of quality components from proven manufacturers. | Visual inspection, functional testing, thermography under load. | According to the component manufacturer's recommendations, or every 3-5 years for critical components. |
| Insufficient ventilation and pollution | Regular cleaning of panels from dust and dirt. Replacing or cleaning air filters. Checking the performance of fans. | Visual inspection, temperature measurement inside and around the panel, air flow check. | Quarterly or every 6 months, depending on operating conditions (dustiness). |
10. Spare Parts and Components
Having the right spare parts available is critical for quick troubleshooting and minimizing downtime. UNITEC-D GmbH offers a wide range of high-quality components that meet international standards.
| Description Details | Specification / Standard | When to Replace | Category UNITEC |
|---|---|---|---|
| Automatic switch | EN 60947-2 / DSTU EN 60947-2:2017. Rated current, operating characteristics (B, C, D). | When triggered by a short circuit, visual damage, overheating of the housing, after a critical overload. | Means of protection and switching |
| Contactor / Starter | EN 60947-4-1 / DSTU EN 60947-4-1:2017. Application category (AC-1, AC-3), rated current. | In case of burning of contacts, mechanical wear, failure, overheating of the coil. | Means of protection and switching |
| Terminal Block / Connection | EN 60947-7-1 / DSTU EN 60947-7-1:2017. Type (screw, spring), current rating, wire cross-section. | In case of oxidation, deformation, traces of overheating, insulation damage. | Terminals and connections |
| Fan for Electrocabinet | Type (axial, centrifugal), performance (m³/h), degree of IP protection, dimensions. | When stopping, increased noise, reduced performance, mechanical damage to the blades. | Climate control systems |
| Air Filters for Cabinets | Filtration class (G2-G4), dimensions. | In case of severe clogging, damage, according to the PPR schedule. | Climate control systems |
| Cables and Conductors | DSTU EN 50525-2-XX, cross section (mm²), insulation type (PVC, XLPE), rated voltage. | In case of damage to the insulation, traces of overheating, color change, constant overcurrent. | Cables and cable products |
To order and select components, please visit the unitec-D electronic catalog.
11. Links
- DSTU EN 50110-1:2017. Operation of electrical installations. General requirements.
- DSTU EN 60947-1:2017. Distribution and control equipment is low voltage. Part 1. General rules.
- DSTU EN 60947-2:2017. Distribution and control equipment is low voltage. Part 2. Automatic switches.
- DSTU EN 50160:2017. Characteristics of power supply voltage in general-purpose electrical networks.
- DSTU IEC 60364-5-52:2016. Electrical installations of buildings. Part 5-52. Selection and installation of electrical equipment. Electrical wiring systems.
- EN 61000-3-2/3, EN 61000-2-4. Electromagnetic compatibility (EMC) standards and limits of harmonic currents.
- ISO 18436. State control and diagnostics of machines. Requirements for qualification and attestation of personnel. Part 7: Thermography.
- Instructions of manufacturers of specific equipment.
- Related UNITEC-D Maintenance Manuals.