Troubleshooting temperature measurement errors: diagnostics of sensors, thermal inertia and transmitter configuration

Technical analysis: Troubleshooting temperature measurement discrepancies: sensor type selection, thermal lag, lead wire

Description of the problem and scope of application

This technique is intended for diagnosis and elimination of temperature measurement errors in industrial control and automation systems. Discrepancies in displays can cause critical deviations in technological processes, lead to product shortages and emergency situations.

Severity Classification:

  • Critical: Error >±5°C in processes with a narrow temperature range
  • Significant: ±2-5°C error in standard manufacturing processes
  • Minor: Error <±2°C in wide tolerance processes

Types of equipment: Thermocouples, RTD thermocouples, 4-20 mA temperature transmitters, temperature controllers, SCADA systems.

Safety measures

ATTENTION: Before starting diagnostics, be sure to take the following safety measures:

  • Use PPE: dielectric gloves, safety glasses, flame-resistant clothing
  • Lockout/Tagout: Disconnect power before working with wiring
  • High Temperature: Allow the equipment to cool down to <60°C
  • Chemical Hazards: Check for aggressive media around sensors
  • Electrical risks: Check insulation when working with 24V DC transmitters

Diagnostic tools are required

ToolSpecificationMeasuring rangePurpose
Digital multimeterAccuracy ±0.1%0-1000V DC/AC, 0-20AChecking voltage, current, resistance
Temperature calibratorAccuracy class 0.05°C-100°C to +1200°CReference temperature source
The ohmmeter is preciseAccuracy ±0.01 Ω0.1-1000 ΩRTD resistance measurement and wiring
mV simulator±0.01 mV-10 to +75 mVThermocouple signal simulation
Thermal imagerAccuracy ±2°C-20°C to +1200°CChecking the temperature distribution
Oscilloscope2 channels, 100 MHz±50VAnalysis of noise and interference

Initial assessment checklist

ParameterWhat to checkRecord the value
Working conditionsProcess temperature, pressure, flow rateCurrent indicators
History of emergency signalsThe last 24 hoursTime, type, duration
Recent changesRepair, adjustment, replacement of sensorsDate, type of work
Environmental conditionsVibration, humidity, temperatureActual values
Wiring statusVisual inspection of cablesDamage, corrosion
Power sourcePower supply voltage of transmitters24V DC ±10%

A systematic scheme of diagnostics

  1. Checking the indication and emergency signals
    • If there are no indications at all → go to point 2
    • If the readings are unstable/noisy → go to item 3
    • If the readings are stable, but inaccurate → go to item 4
  2. Power and signal diagnostics
    • Measure the power supply voltage at the transmitter terminals
    • If <21.6V або >26.4V → power supply problem
    • Measure the circuit current of 4-20 mA
    • If <3.8 mA або >20.5 mA → circuit damage
  3. Analysis of unstable readings
    • Measure noise with an oscilloscope (amplitude >50 mV - unacceptable)
    • Check cable shielding
    • Check ground (resistance <1 Ω)
  4. Measurement accuracy diagnostics
    • Compare with reference thermometer
    • If the error is >±2°C → go to the cause matrix
    • Check sensor calibration

Cause and symptom matrix

SymptomProbable causes (by probability)Diagnostic testExpected result upon confirmation
The readings are higher than the real ones by 5-20°C1. Self-heating of the transmitter
2. Incorrect location of the sensor
3. The influence of external heat
Thermal imager of the transmitter bodyTemperature >70°C
The readings are lower than the real ones by 3-15°C1. Thermal inertia
2. Incorrect sleeve length
3. Poor heat transfer
Dynamic response testResponse time >30 sec
The error varies with the speed of the process1. Thermal inertia of the sensor
2. Incorrect sensor type
3. Insufficient immersion depth
Comparison at different rates of changeThe error increases with rapid changes
Linear error over the entire range1. Incorrect graduation
2. Error in transmitter configuration
3. Zero offset
Calibration in 2-3 pointsConstant offset ±X°C
Non-linear error1. Wrong type of thermocouple
2. Sensor damage
3. Linearization table error
RTD or mV thermocouple resistance testDeviation from standard characteristics

Detailed analysis of the reasons

Incorrect choice of sensor type

The main reason is the inconsistency of the sensor characteristics with the process conditions. Type K thermocouples cannot be used in reducing environments at temperatures >800°C.

Diagnosis: Check sensor specifications against process conditions.

Consequences: Degradation of accuracy, reduction of service life, emergency shutdowns.

Thermal inertia (time constant)

Sensors with a large thermal mass do not have time to track rapid temperature changes. The standard time constant τ63% should be <10 sec for most processes.

Diagnosis: Measure the reaction time to a sudden change of 50°C.

Criteria: τ63% >30 sec indicates a thermal inertia problem.

Resistance of communication lines

For RTD Pt100, the resistance of each wire should not exceed 5 Ω. With a 3-wire connection scheme, the resistance of the wires causes an error of +0.4°C for every 1 Ω.

Diagnosis: Measure the resistance of each wire from the transmitter to the sensor.

Critical values: >10 Ω - critical, 5-10 Ω - needs correction.

Incorrect transmitter configuration

Errors in setting ranges, sensor type, cold junction compensation (for thermocouples) lead to systematic errors.

Diagnosis: Compare the settings with the technical requirements of the process.

Step-by-step elimination procedures

Procedure 1: Sensor selection correction

  1. Determine the real conditions of the process (temperature, pressure, environment)
  2. Select the appropriate sensor type according to DSTU EN 60584-1:2014
  3. For high temperature applications (>800°C) use R or S type thermocouples
  4. For accurate measurements (<200°C) use RTD Pt100 class A
  5. Install a new sensor with an immersion depth of ≥10x the diameter of the sensor
  6. Check the readings by comparison with a reference thermometer

Procedure 2: Reduction of thermal inertia

  1. Measure the current time constant τ63%
  2. If τ63% >20 sec, replace with a smaller diameter sensor
  3. Improve heat transfer: use heat-conducting paste
  4. Check the contact of the sensor with the surface/environment
  5. Measure τ63% again - should be <15 sec
  6. Document the new time constant for the controller setup

Procedure 3: Correction of wiring resistance

  1. Measure the resistance of each wire with the sensor disconnected
  2. If the resistance is >5 Ω, replace the cable with a larger section (min. 1.5 mm²)
  3. For long lines (>100m) use a 4-wire circuit for the RTD
  4. Install an intermediate transmitter near the sensor if the length is >200m
  5. Check the quality of the connections: tightening torque 0.5-0.8 Nm
  6. Measure the error after correction: it should be <±1°C

Procedure 4: Transmitter configuration

  1. Connect a HART communicator or a computer with the appropriate software
  2. Check sensor type settings (RTD: Pt100, TC: K, J type, etc.)
  3. Set the correct measurement range according to technical requirements
  4. For thermocouples, adjust the cold junction compensation
  5. Perform 2-point calibration (0% and 100% scale)
  6. Set damping for 2-5 seconds to reduce noise
  7. Save the configuration and check the operation

Preventive measures

The main reasonPrevention strategyMonitoring methodRecommended interval
Sensor degradationScheduled replacement according to regulationsMonthly accuracy checkRTD: 3 years, TC: 1-2 years
Corrosion of contactsUse of protective sleevesVisual inspection of connectionsEvery 6 months
Calibration driftRegular calibration with standardsComparison with a reference thermometerEvery 12 months
Wiring damageMechanical protection of cablesChecking the resistance of the linesEvery 6 months
Electrical interferenceProper shielding and groundingOscilloscope noise analysisWhen instability is detected

Spare parts and components

Description of the partSpecificationWhen to replaceCategory UNITEC
RTD Pt100 class A3-wire, diameter 6mm, L=100mmIf the error is >±0.5°CTemperature sensors
K-type thermocoupleDiameter 3 mm, length 200 mmAt degradation >±2°CTemperature sensors
Temperature transmitter4-20mA, HART, IP67In case of calibration failuresTransmitters and converters
Protective sleeveStainless steel 316L, thread G1/2In case of corrosion or mechanical damageFittings and adapters
Instrument cable3×1.5mm², shielded, -40°C to +200°CIf the resistance is >5Ω per 100 mCables and connectors
Terminal boxIP65, polycarbonateIn case of breach of tightnessElectrical engineering

To order spare parts, visit the UNITEC-D electronic catalog: UNITEC-D E-Catalog

Reference materials

  • DSTU EN 60584-1:2014 - Thermocouples. Part 1. EMF specifications and tolerances
  • DSTU IEC 60751:2009 - Industrial platinum resistance thermometers
  • ISO 5168:2005 - Measurement of fluid flow - Procedures for estimating uncertainties
  • EN 50446:2008 - General requirements for methods of measuring electromagnetic fields
  • Transmitter manufacturers' manuals (Rosemount, Endress+Hauser, WIKA)
  • UNITEC Maintenance Guides - Calibration of measuring devices
  • UNITEC Maintenance Guides - Protection against electromagnetic interference

Related Articles