Description of the problem and scope of application
This technique is intended for diagnosis and elimination of temperature measurement errors in industrial control and automation systems. Discrepancies in displays can cause critical deviations in technological processes, lead to product shortages and emergency situations.
Severity Classification:
- Critical: Error >±5°C in processes with a narrow temperature range
- Significant: ±2-5°C error in standard manufacturing processes
- Minor: Error <±2°C in wide tolerance processes
Types of equipment: Thermocouples, RTD thermocouples, 4-20 mA temperature transmitters, temperature controllers, SCADA systems.
Safety measures
ATTENTION: Before starting diagnostics, be sure to take the following safety measures:
- Use PPE: dielectric gloves, safety glasses, flame-resistant clothing
- Lockout/Tagout: Disconnect power before working with wiring
- High Temperature: Allow the equipment to cool down to <60°C
- Chemical Hazards: Check for aggressive media around sensors
- Electrical risks: Check insulation when working with 24V DC transmitters
Diagnostic tools are required
| Tool | Specification | Measuring range | Purpose |
|---|---|---|---|
| Digital multimeter | Accuracy ±0.1% | 0-1000V DC/AC, 0-20A | Checking voltage, current, resistance |
| Temperature calibrator | Accuracy class 0.05°C | -100°C to +1200°C | Reference temperature source |
| The ohmmeter is precise | Accuracy ±0.01 Ω | 0.1-1000 Ω | RTD resistance measurement and wiring |
| mV simulator | ±0.01 mV | -10 to +75 mV | Thermocouple signal simulation |
| Thermal imager | Accuracy ±2°C | -20°C to +1200°C | Checking the temperature distribution |
| Oscilloscope | 2 channels, 100 MHz | ±50V | Analysis of noise and interference |
Initial assessment checklist
| Parameter | What to check | Record the value |
|---|---|---|
| Working conditions | Process temperature, pressure, flow rate | Current indicators |
| History of emergency signals | The last 24 hours | Time, type, duration |
| Recent changes | Repair, adjustment, replacement of sensors | Date, type of work |
| Environmental conditions | Vibration, humidity, temperature | Actual values |
| Wiring status | Visual inspection of cables | Damage, corrosion |
| Power source | Power supply voltage of transmitters | 24V DC ±10% |
A systematic scheme of diagnostics
- Checking the indication and emergency signals
- If there are no indications at all → go to point 2
- If the readings are unstable/noisy → go to item 3
- If the readings are stable, but inaccurate → go to item 4
- Power and signal diagnostics
- Measure the power supply voltage at the transmitter terminals
- If <21.6V або >26.4V → power supply problem
- Measure the circuit current of 4-20 mA
- If <3.8 mA або >20.5 mA → circuit damage
- Analysis of unstable readings
- Measure noise with an oscilloscope (amplitude >50 mV - unacceptable)
- Check cable shielding
- Check ground (resistance <1 Ω)
- Measurement accuracy diagnostics
- Compare with reference thermometer
- If the error is >±2°C → go to the cause matrix
- Check sensor calibration
Cause and symptom matrix
| Symptom | Probable causes (by probability) | Diagnostic test | Expected result upon confirmation |
|---|---|---|---|
| The readings are higher than the real ones by 5-20°C | 1. Self-heating of the transmitter 2. Incorrect location of the sensor 3. The influence of external heat | Thermal imager of the transmitter body | Temperature >70°C |
| The readings are lower than the real ones by 3-15°C | 1. Thermal inertia 2. Incorrect sleeve length 3. Poor heat transfer | Dynamic response test | Response time >30 sec |
| The error varies with the speed of the process | 1. Thermal inertia of the sensor 2. Incorrect sensor type 3. Insufficient immersion depth | Comparison at different rates of change | The error increases with rapid changes |
| Linear error over the entire range | 1. Incorrect graduation 2. Error in transmitter configuration 3. Zero offset | Calibration in 2-3 points | Constant offset ±X°C |
| Non-linear error | 1. Wrong type of thermocouple 2. Sensor damage 3. Linearization table error | RTD or mV thermocouple resistance test | Deviation from standard characteristics |
Detailed analysis of the reasons
Incorrect choice of sensor type
The main reason is the inconsistency of the sensor characteristics with the process conditions. Type K thermocouples cannot be used in reducing environments at temperatures >800°C.
Diagnosis: Check sensor specifications against process conditions.
Consequences: Degradation of accuracy, reduction of service life, emergency shutdowns.
Thermal inertia (time constant)
Sensors with a large thermal mass do not have time to track rapid temperature changes. The standard time constant τ63% should be <10 sec for most processes.
Diagnosis: Measure the reaction time to a sudden change of 50°C.
Criteria: τ63% >30 sec indicates a thermal inertia problem.
Resistance of communication lines
For RTD Pt100, the resistance of each wire should not exceed 5 Ω. With a 3-wire connection scheme, the resistance of the wires causes an error of +0.4°C for every 1 Ω.
Diagnosis: Measure the resistance of each wire from the transmitter to the sensor.
Critical values: >10 Ω - critical, 5-10 Ω - needs correction.
Incorrect transmitter configuration
Errors in setting ranges, sensor type, cold junction compensation (for thermocouples) lead to systematic errors.
Diagnosis: Compare the settings with the technical requirements of the process.
Step-by-step elimination procedures
Procedure 1: Sensor selection correction
- Determine the real conditions of the process (temperature, pressure, environment)
- Select the appropriate sensor type according to DSTU EN 60584-1:2014
- For high temperature applications (>800°C) use R or S type thermocouples
- For accurate measurements (<200°C) use RTD Pt100 class A
- Install a new sensor with an immersion depth of ≥10x the diameter of the sensor
- Check the readings by comparison with a reference thermometer
Procedure 2: Reduction of thermal inertia
- Measure the current time constant τ63%
- If τ63% >20 sec, replace with a smaller diameter sensor
- Improve heat transfer: use heat-conducting paste
- Check the contact of the sensor with the surface/environment
- Measure τ63% again - should be <15 sec
- Document the new time constant for the controller setup
Procedure 3: Correction of wiring resistance
- Measure the resistance of each wire with the sensor disconnected
- If the resistance is >5 Ω, replace the cable with a larger section (min. 1.5 mm²)
- For long lines (>100m) use a 4-wire circuit for the RTD
- Install an intermediate transmitter near the sensor if the length is >200m
- Check the quality of the connections: tightening torque 0.5-0.8 Nm
- Measure the error after correction: it should be <±1°C
Procedure 4: Transmitter configuration
- Connect a HART communicator or a computer with the appropriate software
- Check sensor type settings (RTD: Pt100, TC: K, J type, etc.)
- Set the correct measurement range according to technical requirements
- For thermocouples, adjust the cold junction compensation
- Perform 2-point calibration (0% and 100% scale)
- Set damping for 2-5 seconds to reduce noise
- Save the configuration and check the operation
Preventive measures
| The main reason | Prevention strategy | Monitoring method | Recommended interval |
|---|---|---|---|
| Sensor degradation | Scheduled replacement according to regulations | Monthly accuracy check | RTD: 3 years, TC: 1-2 years |
| Corrosion of contacts | Use of protective sleeves | Visual inspection of connections | Every 6 months |
| Calibration drift | Regular calibration with standards | Comparison with a reference thermometer | Every 12 months |
| Wiring damage | Mechanical protection of cables | Checking the resistance of the lines | Every 6 months |
| Electrical interference | Proper shielding and grounding | Oscilloscope noise analysis | When instability is detected |
Spare parts and components
| Description of the part | Specification | When to replace | Category UNITEC |
|---|---|---|---|
| RTD Pt100 class A | 3-wire, diameter 6mm, L=100mm | If the error is >±0.5°C | Temperature sensors |
| K-type thermocouple | Diameter 3 mm, length 200 mm | At degradation >±2°C | Temperature sensors |
| Temperature transmitter | 4-20mA, HART, IP67 | In case of calibration failures | Transmitters and converters |
| Protective sleeve | Stainless steel 316L, thread G1/2 | In case of corrosion or mechanical damage | Fittings and adapters |
| Instrument cable | 3×1.5mm², shielded, -40°C to +200°C | If the resistance is >5Ω per 100 m | Cables and connectors |
| Terminal box | IP65, polycarbonate | In case of breach of tightness | Electrical engineering |
To order spare parts, visit the UNITEC-D electronic catalog: UNITEC-D E-Catalog
Reference materials
- DSTU EN 60584-1:2014 - Thermocouples. Part 1. EMF specifications and tolerances
- DSTU IEC 60751:2009 - Industrial platinum resistance thermometers
- ISO 5168:2005 - Measurement of fluid flow - Procedures for estimating uncertainties
- EN 50446:2008 - General requirements for methods of measuring electromagnetic fields
- Transmitter manufacturers' manuals (Rosemount, Endress+Hauser, WIKA)
- UNITEC Maintenance Guides - Calibration of measuring devices
- UNITEC Maintenance Guides - Protection against electromagnetic interference