Cooling Water System Maintenance Manual: Biocide Dosing, Corrosion Coupon Analysis, and Purge Optimization

Technical analysis: Cooling water treatment: biocide dosing, corrosion coupon analysis, and blowdown optimization

1. Scope and purpose

This manual covers critical maintenance procedures for open circulating cooling water systems used in industrial settings including the automotive, chemical, food and energy industries. The goal is to prevent biofouling, minimize corrosion, and optimize water use efficiency through blowdown control. The correct application of these procedures is mandatory to ensure the reliable operation of the equipment, prolong its service life and maintain the efficiency of heat exchange. Maintenance should be carried out regularly according to the schedule, as well as when deviations in water parameters are detected.

2. Precautions

CAUTION: Working with chemicals and systems under pressure requires strict adherence to safety rules. Failure to do so could result in serious personal injury or equipment damage.

PERSONAL PROTECTION: Be sure to wear safety glasses, chemically resistant gloves (such as nitrile or neoprene), protective clothing, and, if necessary, respiratory protection according to the Material Safety Data Sheets (MSDS) for all reagents.

LOCKOUT/TAGOUT: Before working on pumps, valves, or electrical components of the cooling water system, ensure that power sources are isolated and locked out/tagout in accordance with the company's safety procedures (DSTU standard EN 1037:2004).

CHEMICAL SAFETY: Always add chemicals slowly and carefully to avoid splashing. Have emergency showers and eyewash stations handy. Store chemicals according to manufacturer's recommendations, away from incompatible materials.

3. Necessary tools and materials

Name of tool/material Specification Quantity
Dosing pump for biocides Suitable performance (e.g. 1-10 l/h) and pressure (up to 10 bar), chemically resistant materials 1
Corrosive coupons Appropriate material (eg mild steel (SAE 1010), copper, brass); precisely weighed, certified (ISO 10002) 6-12 pieces/year (for rotation)
Holder of corrosion coupons (rack) For installing 3-6 coupons, chemically resistant 1-2
Kit for titration To determine the concentration of inhibitors, alkalinity, hardness, chlorine 1
pH meter Range 0-14 pH, accuracy ±0.02 pH, calibrated 1
Conductometer Range 0-20 mS/cm, accuracy ±1% of full scale, calibrated 1
Thermometer Range 0-100 °C, accuracy ±0.5 °C 1
Portable microbiological test (dip slides) For the total count of bacteria and fungi 1 package (10 pcs.)
Flow meter (manual) Graduated cylinder (1000 ml) and stopwatch 1
Libra is analytical Accuracy up to 0.0001 g (for weighing coupons) 1 (laboratory)
Distilled water For coupon cleaning and calibration 5 liters
Specialized reagents for cleaning coupons According to ASTM G1 1 set
Wrenches Set from 8 to 32 mm 1
Screwdrivers A set of flat and cross-shaped 1
Torque wrench Range 5-50 Nm, calibrated (according to ISO 6789) 1
Protective apron/suit Chemically stable 1
Means for cleaning Rags, brushes, bucket As needed

4. Checklist before starting maintenance

Item Verification Acceptance/rejection criteria Notes
Chemical composition of water Collect water samples from the system and perform an express analysis (pH, conductivity, alkalinity, hardness) pH 7.5-8.5; Conductivity within working cycles of concentration; Alkalinity and hardness within the limits recommended for inhibitors Record the current values
Presence of biocides and inhibitors Check chemical levels in dosing containers Sufficient supply for planned dosing and reserve Provide replenishment as needed
Dosing pumps Visual inspection of pumps, pipelines and injection sites No leaks, corrosion, clogging, mechanical damage. Pumps work evenly. Check the performance settings of the pumps
Filters Check the pressure on the filters, visual inspection Pressure drop within acceptable limits. No excessive pollution. Schedule cleaning or replacement if necessary
Cooling towers and heat exchangers Visual inspection for visible biofouling, deposits or corrosion Clean surfaces, no slime, algae, rust Document any anomalies
Blowing lines Check the operation of the purge valves (automatic and manual) Valves function freely, without leaks, open/close fully
Means of protection Check the availability and condition of necessary PPE The PPE is in good condition and has not expired

5. Step-by-step procedure

5.1. Dosage of biocides

  1. Preparation and dose calculation:
    • Determine the total volume of the cooling water system (cooling tower, pipelines, heat exchangers). This information is usually available in the technical documentation of the system.
    • Calculate the required amount of biocide for shock dosing according to the manufacturer's recommendations and the current state of the system (based on microbiological analysis). For inorganic biocides, it can be 50-200 ppm, for oxidative biocides - 1-5 ppm of free chlorine. Error: underestimating the size of the system will lead to insufficient efficiency.
  2. Dosing pump calibration:
    • SAFETY: Make sure the dosing pump is de-energized and isolated if it needs to be disconnected for calibration. Use PPE.
    • Shut off the biocide supply to the system.
    • Connect a calibrated graduated cylinder (eg 1000 ml) to the output line of the pump.
    • Start the pump and measure the volume of biocide dispensed in 1 minute. For example, if it is necessary to dose 5 l/h, in 1 minute the volume should be approximately 83 ml.
    • Adjust pump settings (pulse frequency, stroke length) until desired performance is achieved.
    • Error: Using an uncalibrated pump will result in over- or underdosing.
  3. Biocide injection:
    • Provide biocide injection at a point in the system with effective mixing (eg cooling tower catch basin or circulation pump suction).
    • For shock dosing: Add the calculated amount of biocide over a short period (eg 15-30 minutes) according to a schedule (eg once a week or twice a week).
    • For continuous dosing (if applicable): Set the pump to a constant low dosing rate.
    • Visual indicator: uniform dissolution of the biocide in water.
  4. Effectiveness monitoring:
    • After 12-24 hours after dosing, take a water sample and conduct a microbiological analysis using test strips (dip slides).
    • Acceptable result: a significant reduction in the number of colonies (less than 104 CFU/ml).
    • Error: lack of monitoring after dosing does not allow to evaluate effectiveness.

5.2. Analysis of corrosion coupons

  1. Installation of corrosion coupons:
    • SAFETY: Use PPE. Make sure the cooling water system is working normally.
    • Choose a representative place to install the coupon holder where the water flow speed is 0.5-1.5 m/s. Usually this is a side flow (bypass) or a section of the pipeline after the pump.
    • Carefully place the pre-weighed, cleaned and identified corrosion coupons into the holder. Fix them so that they do not touch each other and the walls of the holder.
    • Record the installation date, coupon identification numbers, and initial weight (to the nearest 0.0001 g).
    • Bug: misplacing coupons or damaging them during installation will distort results.
  2. Exposure:
    • Leave coupons in the system for the standard exposure period recommended by the manufacturer or according to internal procedures (usually 30, 60 or 90 days).
  3. Extracting and cleaning coupons:
    • After the exposure period, again SAFETY: isolate the coupon area, release pressure and drain the water. Use PPE.
    • Carefully remove the coupons from the holder, avoiding mechanical damage.
    • Clean the coupons of deposits and corrosion products in accordance with ASTM G1 (for example, with a chemical solution to remove corrosion products without affecting the base metal).
    • After cleaning, rinse the coupons thoroughly with distilled water, dry and place in a desiccator.
    • Error: Aggressive mechanical cleaning or incomplete removal of corrosion products will lead to false results.
  4. Reweighing and calculation:
    • Reweigh each coupon to the nearest 0.0001 g.
    • Calculate the mass loss for each coupon.
    • Using the formula, calculate the corrosion rate in MPY (mils per year) or mm/year:
    • Corrosion Rate (MPY) = (Massinitial - Massfinal) × 22300 / (Area × Density × Time)
    • Where: Area is the surface area of the coupon (inch2), Density is the metal density of the coupon (g/cm3), Time is the exposure time (days).
    • Acceptable values: for mild steel, the corrosion rate should be less than 3 MPY (0.076 mm/year); for copper alloys – less than 0.5 MPY (0.013 mm/year).
    • Document all results. Error: Arithmetic errors or use of incorrect units of measurement.

5.3. Blowdown optimization

  1. Monitoring water parameters:
    • Regularly measure conductivity (μS/cm), total dissolved solids (TDS, ppm), pH and temperature (°C) of cooling water and makeup water.
    • Record these values.
  2. Calculation of concentration cycles (CC):
    • Concentration cycles (CC) = Conductivitycooling water / Conductivityfeed water.
    • Target CCs depend on the quality of the feed water and the type of inhibitors used (typically 3-6 for open systems).
    • Error: ignoring the quality of the feed water when calculating the CC.
  3. Auto Purge Settings:
    • If the system is equipped with an automatic purge controller, set the desired upper conductivity limit (eg 2000-3000 µS/cm for a CC=5 system with 400 µS/cm feed water).
    • Check the operation of the purge solenoid valve and conductivity sensor.
    • Visual indicator: the purge valve opens when the conductivity reaches the set value and closes when it drops.
  4. Manual purging (in the absence of automation):
    • SAFETY: Always monitor the water level in the cooling tower during manual purging to avoid drying out the pumps.
    • Calculate the required purge volume to maintain the CC. For example, if CC = 4, then 25% of the evaporation volume should be purging.
    • Open the manual purge valve for the set time or until the desired conductivity level is reached.
    • After purging is complete, close the valve and check the water parameters.
    • Error: excessive purging leads to excessive consumption of water and chemicals; insufficient - to the accumulation of salts and corrosion.
  5. Check and Adjust:
    • Within a few days of purge setup, monitor system conductivity and feed water flow.
    • If necessary, adjust purge settings to maintain stable CCs and minimize water wastage.

6. Post-service verification checklist

Test/Check Expected result Actual result Pass/Fail
Biocide level in the system Compliance with the recommended concentration (by test strips or titration)
Dosing pump operation The pump works according to the established schedule, without leaks, performance according to calibration
pH of the cooling water Within 7.5 - 8.5 pH
Conductivity of cooling water Stable, within the established concentration cycles (for example, 2000-3000 μS/cm)
No leaks Visually checked all connections, pumps, pipelines
Visual inspection of the system No new fouling, deposits, corrosion in the cooling tower and available heat exchangers
Records All performed work, measurements and results are documented

7. Troubleshooting guide

Symptom Probable cause Corrective action
High microbiological pollution (mucus, algae) Insufficient dosage of biocide; uneven distribution of the biocide; development of resistant strains; insufficient purging Increase the dose of biocide or the frequency of dosing; check injection and mixing points; consider an alternative type of biocide; carry out shock disinfection of the system; optimize purging.
High corrosion rate (based on coupon results) Insufficient concentration of corrosion inhibitors; high water conductivity; low pH; high oxygen content; biologically induced corrosion (MIC) Increase the dose of inhibitors; optimize concentration cycles due to increased purging; adjust the pH (if it is provided by the strategy); check aeration; apply appropriate biocides.
Excessive formation of deposits (scale) Excessively high cycles of concentration; insufficient dosage of dispersants/antiscalers; high hardness of feed water Increase purging to reduce CC; check and adjust the dosage of dispersants; consider preliminary treatment of feed water (softening).
High feed water consumption Excessive purging; leaks in the system; uncontrolled overflow of water Optimize purging settings (reduce); detect and eliminate leaks in pipelines, valves, heat exchangers; check the water level in the cooling tower pool.
Unstable pH of water Irregular purging; fluctuations in the quality of feed water; insufficient alkalinity; biological activity Optimize purging; to stabilize the quality of feed water; adjust the dosage of pH regulators (if used); control microbiological activity.

8. Recommended maintenance schedule

Task Frequency Estimated duration Qualification level
Visual inspection of the cooling system Every day 15 min Operator/Technician
Checking and adjusting biocidal dosage (dip slides) Every week 30 min Technician
Measurement of pH, conductivity, temperature 3 times a week 15 min Operator/Technician
Comprehensive chemical analysis of water (titered tests) Every month 1-2 hours Chemist/Experienced technician
Replacement and analysis of corrosion coupons Quarterly (every 90 days) 2-4 hours (without laboratory analysis) Experienced technician
Calibration of dosing pumps Every quarter 1-2 hours/pump Technician
Cleaning/inspection of cooling tower pool and filling Annually or as needed 1-2 working days A team of technicians
Calibration of sensors (pH, conductivity) Annually or as needed 1 hour/sensor Engineer of KVPiA

9. Directory of spare parts

Part description Typical specification Category UNITEC
Peristaltic dosing pump Productivity 0.1-10 l/h, pressure up to 8 bar, PP/PVDF body Pumps
Membranes for dosing pumps Material PTFE/EPDM, for specific pump model Components for pumps
pH sensor Combined, range 0-14 pH, temperature 0-80°C, connection PG13.5 Sensors
Conductivity sensor Range 0-20 mS/cm, cell constant K=1.0, body material PP/PVDF Sensors
Calibration solutions for the pH meter pH 4.01, 7.00, 10.01 Consumables
Calibration solutions for the conductometer 1413 μS/cm, 12.88 mS/cm Consumables
Corrosive coupons Mild steel (SAE 1010), copper, brass; dimensions 76.2 x 25.4 x 3.2 mm Consumables
Holder of corrosion coupons PVC, for 3-6 coupons, 3/4" NPT connection Accessories
Electromagnetic valve DN25, normally closed, 24V DC, material brass/stainless steel. steel Valves
Mesh/cartridge filters Appropriate micron size (e.g. 50-100 µm), material stainless steel/polypropylene Filters
Pipelines and fittings PVC, PE, stainless steel, suitable diameters Pipelines

To order spare parts and familiarize yourself with the full range of products, visit the electronic catalog UNITEC-D.

10. Links

  • DSTU EN 1037:2004 Machine safety. Prevention of unexpected start.
  • ISO 10002:2018 Quality management. Consumer satisfaction. Guidelines for working with complaints in organizations.
  • ASTM G1-03(2017) Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens.
  • EN 806-2:2005 Technical conditions for drinking water supply systems for buildings. Part 2: Design.
  • Recommendations of the manufacturer of the cooling water system (OEM documentation).
  • Safety data sheets of chemical reagents (MSDS/SDS).

Related Articles