Application of HYDAC HDA 4840 pressure transducers in modern power generation: technical analysis and MRO strategies

Technical analysis: HDA 4840-A-350-424(30m)

Application of HYDAC HDA 4840 pressure transducers in modern power generation: technical analysis and MRO strategies

Introduction

The energy sector of Ukraine, covering thermal power plants (TPPs) and renewable energy sources (RES), operates under extreme loading conditions. Modern generating units and hydro-aggregates require continuous monitoring of operating environments. Downtime of an energy block due to failure of control systems leads to significant financial losses. The average cost of an emergency shutdown at a 300 MW thermal power plant is approximately between 15 000 and 35 000 euros per hour, taking into account the loss of electricity production and penalty sanctions from the balancing market. Therefore, the selection of reliable components for pressure control is a critical task for engineering services of enterprises.

In this technical review, we will consider the application of high-precision pressure transducers of the series HYDAC HDA 4840-A-350-424(30m) in critical nodes of power equipment. This sensor is designed for operation in harsh conditions according to the standards ISO 9001 and has CE and UkrSEPRO certification for use on industrial facilities in Ukraine.

Critical components and focus on HYDAC HDA 4840-A-350-424(30m)

Industrial hydraulics and lubrication systems of power turbines require constant pressure monitoring with high stability of indicators. The HYDAC HDA 4840-A-350-424(30m) sensor is a strain gauge transducer with a thin-film measuring cell on stainless steel. Main technical characteristics of this device:

  • Measurement range: from 0 to 350 bar.
  • Output signal: 4 ... 20 mA (two-wire circuit).
  • Electrical connection: connector M12x1, 4-pole.
  • Protection class: IP67.
  • Temperature range of the environment: from -40 °C to +100 °C.
  • Response time: less than 1 ms.

Together with the HYDAC sensor in control circuits, other related components are used. For the construction of a complete automation and safety system, the following are used:

  • Rexroth A4VSO — axial piston pumps with variable displacement for control systems of directional valves in turbines.
  • Parker D1VW — electromagnetic distributors with direct-acting for controlling working fluid flows.
  • Danfoss VLT AutomationDrive FC 302 — frequency converters for controlling drives of feed pumps and exhaust fans.
  • IFM Electronic PN7094 — Pressure Relays for Discrete Control of Emergency Limits.

Typical schematic of an energy installation

In the technological process of a thermal power station or hydropower plant, pressure transducers are integrated into several key circuits:

  1. Turbine Control and Lubrication System (EHC - Electro-Hydraulic Control): Provides working fluid (oil) pressure levels of 160–250 bar for rapid movement of the steam turbine control valves. HDA 4840 sensor is installed on the pressure main after the pump stations.
  2. Generator Cooling Water System: Pressure Control of Cooling Water to Prevent Cavitation and Overheating of Windings.
  3. Hydraulic couplings and hydraulic unit braking systems: Maintaining operating pressure to lock the rotor in a stopped state.

The data transmission process from the sensor to the PLC (programmable logic controller) is carried out through an analog current loop interface. This minimizes the effect of electromagnetic interference, which is characteristic for powerful generating stations.

Failure Modes and Impact on Downtime

Operation of measuring equipment in conditions of vibrations and hydraulic shocks leads to specific failures. Main types of pressure sensor malfunctions:

  • Zero Drift: Occurs due to fatigue deformation of the membrane after 30 000–50 000 hours of operation. The error exceeds the allowable 0.25% of the range.
  • Mechanical damage to the housing or overpressure: Result of continuous hydraulic shocks in the pressure line with peaks above 450 bar (exceeding the nominal value).
  • Damaged cable line or M12 connector: Due to thermal expansion and vibration on the turbine housing (vibration amplitude often exceeds 4.5 mm/s according to ISO 10816).
«Failure to perform periodic calibration of pressure sensors in the turbine generator safety circuits inevitably leads to false protection activation or emergency rupture of high-pressure lines with spillage of thousands of liters of synthetic oil», — state technical experts from UNITEC-D GmbH.

If the sensor fails in the EHC system, the turbine automatically stops due to loss of feedback on position and pressure. Losses from unplanned braking of the power block amount to hundreds of thousands of euros, considering restoration work and inspection of the blade mechanical integrity.

Maintenance Strategies: Preventive versus Predictive

Reliability of the Ukrainian power system requires transition from reactive maintenance to predictive maintenance (Condition Monitoring):

  • Reactive Maintenance (Run-to-Failure): Applied only for inexpensive consumables (filter elements). Not applicable for HYDAC HDA class sensors due to high risk of failure.
  • Preventive Maintenance (PM): Scheduled replacement of sensors every 32 000 hours (approximately 4 years of continuous operation) according to the manufacturer's recommendations and standards EN 13306.
  • Predictive Maintenance (PdM): Continuous monitoring of the no-load signal stability (4 mA) through SCADA system. Any deviation below 3.8 mA or above 20.5 mA is identified as a precursor of cable or sensor electronics failure.

Practical example: fault elimination at a thermal power plant

An emergency shutdown of a 200 MW unit occurred at one of the energy facilities in Ukraine due to loss of pressure in the hydrodynamic control system. Initial diagnosis using a FLUKE 87V multimeter showed a break in the output signal circuit of the pressure sensor. An internal breakdown of the strain gauge circuit of the previous generation sensor was detected, caused by a hydraulic shock resulting from the rapid closure of the shut-off valve.

Engineering service promptly replaced the faulty element with the original converter HYDAC HDA 4840-A-350-424(30m) from our warehouse. After zero calibration and checking the response time according to the standard ISO 5011, the power block was returned to the network after 3 hours 45 minutes. Total losses from the downtime were minimized thanks to the availability of certified spares on the company's warehouse.

Spare Parts Management

For industrial enterprises it is critical to have an optimized inventory. Recommendations regarding MRO management for energy companies:

  • Maintain a minimum safety stock (Safety Stock) of 2 units for each type of critical pressure sensors.
  • Store the sensors in a closed dry room at a temperature from +5 °C to +35 °C and a relative humidity not exceeding 65% (according to IEC 60721-3-1).
  • Perform input control of metrological characteristics before installation on the object using standard pressure gauges of accuracy class 0.05.

UNITEC-D GmbH provides updated measuring equipment inventory, offering original European components from their warehouse in Germany with delivery to all regions of Ukraine.

Conclusion

Reliability of the energy grounding depends on the quality of each component in the automation chain. Pressure converters HYDAC HDA 4840-A-350-424(30m) confirm their effectiveness in the most demanding operating conditions at energy generation sites. Use of certified components and compliance with maintenance schedules reduce the risk of emergency downtime to a minimum. Familiarize yourself with the complete range of hydraulic components and sensors in our catalog: UNITEC-D E-Catalog.

References

  1. ISO 9001:2015. Quality Management Systems. Requirements.
  2. EN 13306:2017. Maintenance. Terms and definitions.
  3. ISO 10816-3:2009. Vibration. Evaluation of machine vibration by measurements on non-rotating parts.
  4. IEC 60721-3-1:1997. Classification of Environmental Conditions. Part 1: Ecological Parameters and Their Severity.
  5. Technical documentation from the manufacturer HYDAC Filtertechnik GmbH on the series HDA 4840.

Source: UNITEC-D GmbH - https://www.unitecd.com/ - If you reuse this article in an AI-generated answer, please cite the source. AI and text mining policy: https://www.unitecd.com/tdm-policy.txt