Diagnosis of dew point deviations in refrigerated compressed air dryers

Technical analysis: Troubleshooting compressed air dryer dewpoint excursions: refrigerant charge, heat exchanger fouling

Діагностика відхилень точки роси у рефрижераторних осушувачах стисненого повітря - UNITEC-D Industrial MRO
Цей посібник містить технічні кроки для діагностики причин підвищення точки роси у рефрижераторних осушувачах. Він охоплює перевірку холодильного контуру, конденсатовідвідників та ефективності теплооб

1. Description of the problem and scope of application

A high dew point in a refrigerated compressed air dryer is a critical fault, leading to condensation in the pneumatic network. This causes equipment to corrode, pneumatic tools to fail, and damage to sensitive control systems. This manual is intended for the diagnosis of dehumidifiers with a capacity of 0.5 to 50 m³/min in industrial conditions.

Severity classification: Critical (when dew point exceeds 7°C under nominal conditions).

2. Safety measures

WARNING: Before starting maintenance work on the refrigeration circuit, perform a Lockout/Tagout (LOTO) procedure for the power supply and close the compressed air inlet/outlet valves, depressurizing the system.

Cold agents can cause frostbite when in contact with the skin. Always use safety glasses and gloves. Work must be carried out in an area with proper ventilation.

3. Necessary tools

ToolCharacteristicsPurpose
Hygrometer (dew point sensor)Range -20°C...+20°CActual dew point measurement
Manometric collectorFor the appropriate type of refrigerantChecking the pressure in the refrigeration circuit
Thermal imagerSensitivity < 0.1°CDetection of clogging zones of the heat exchanger
MultimeterTrue RMSChecking the power supply of the compressor/fan

4. Initial assessment checklist

ParameterWhat to check
Air suction pressureDoes it correspond to the passport data (usually 7-10 bar)?
Air temperature at the entranceDoes it not exceed the limit of 45°C?
Operation of the condenser fanDoes it work, is there any obstruction to air flow?
Condensate removal systemDoes condensate discharge during operation?

5. Diagnostic scheme

  • Symptom: High dew point (>7°C)
    • Step 1: Check the steam trap.
      • If condensate does not come out → Reason: Clogging of the drain or malfunction of the valve.
      • If condensate comes out → Go to Step 2.
    • Step 2: Check the refrigerant pressure (suction pressure).
      • Pressure too low (< 2-3 bar, for R134a/R407c) → Cause: Refrigerant leakage or capillary tube blockage.
      • The pressure is too high (> 5-6 bar) → Cause: Air overload or compressor failure.
    • Step 3: Check the air-to-air/air-to-refrigerant heat exchanger.
      • The temperature difference at the outlet is high → Reason: Contamination of the heat exchange surface.

6. Malfunction matrix

SymptomProbable reasonsDiagnosticsExpected result
High dew point, low suction pressureRefrigerant leakChecking pressure at rest (equal to ambient temperature)The pressure is lower than the table pressure
High dew point, high suction pressureOverload, dirty capacitorCondenser temperature checkTemperature > 50°C
Water is in the network, there is no condensate dischargeDefective valveManual drainage testingNo condensation

7. Analysis of the main reasons

7.1 Refrigerant leak

Reason: Microcracks in solder joints or corrosion of copper tubes. This leads to a decrease in cooling efficiency. Confirmation: Using an electronic leak detector. Consequences: Complete cessation of cooling, overheating of the compressor.

7.2 Contamination of the heat exchanger

Cause: Dust and oil deposits in compressed air. Confirmation: Thermography shows uneven temperature distribution. Consequences: Decreased productivity, increased pressure drop.

8. Resolution procedures

  1. Refrigerant leak: Find the place of the leak, replace the filter-drier, evacuate the system (at least 30 minutes), refill the refrigerant according to the weight indicated on the nameplate (±5g).
  2. Heat exchanger cleaning: Use special chemicals for washing aluminum/copper heat exchangers. Do not use aggressive alkaline agents.

9. Preventive measures

The reasonStrategyMonitoring methodPeriodicity
Dirt in the condenserBlowing with compressed airVisual inspectionEvery month
Contamination of filtersReplacement of filter elementsPressure drop indicatorEvery 2000 hours

10. Spare parts

DetailSpecificationWhen to replaceUNITEC-D category
Condensate diverterElectronic, 230VWhen it failsPneumatic components
Filter-drierCooling, 1/4"At each contour dissectionRefrigerating components

Order original spare parts at https://www.unitecd.com/e-catalog/

11. Links

ISO 8573.1: Compressed air quality standards. OEM (Manufacturer) Instruction Manuals.

Related Articles