1. Problem Description and Area of Application
This guide is intended for the diagnosis and correction of vibrations and shuddering of the control valve. These symptoms may occur in various types of industrial equipment such as flow control systems, temperature regulation systems, pressure regulation systems, and in chemical production systems. The importance of this issue is classified as critical, as valve vibrations may lead to unexpected leaks, process instability, and in some cases, to emergency situations.
2. Precautionary measures for safety
Personal Protective Equipment Requirements: During diagnostics, special protective clothing must be used, including work gloves, goggles, and pants with static electrical properties.
Lockout/Tagout: Before starting the diagnostics of the equipment, turn off the power supply, apply lockout tags, and perform a check for absence of electrical power.
Warning about protective elements: In case of electrical or gas accumulations, contact with the equipment may result in injuries or electric shock.
3. Required diagnostic tools
| Tool Name | Model/Specification | Measurement range | Objective |
|---|---|---|---|
| Multimeter | Fluke 87V | 0-2000 mA, 0-600 V | Measurement of electrical parameters, voltage, current, resistance |
| Vibration Analyzer | Keysight 35670A | 0-50,000 Hz | Vibration measurement, fault detection |
| Thermocamera | Fluke TiS10 | -20°C to 500°C | Detection of uneven heating |
| Positioner | Siemens Simatic S7-1200 | 0-10 V, 4-20 mA | Positioner Setup for Valve Position Stabilization |
4. First Review: Checklist for the Start of Diagnosis
| Item | Description |
|---|---|
| 1 | Check the temperature around the valve and the fluid transport path. |
| 2 | Record the values of pressure, temperature and evaporation level. |
| 3 | Check the status of the positioner and the connection with the control system. |
| 4 | Measure the valve vibration and path. |
| 5 | Record the alarm history and system messages. |
5. Systematic Diagnostic Scheme
- Symptom: Valve oscillation when signal changes.
- Check the positioner against production requirements.
- Measure the valve vibration.
- If vibration exceeds 4.5 mm/s, check the battery.
- Symptom: Vibration increases with increasing pressure.
- Check the system pressure.
- Measure the friction level in the pusher.
- If friction exceeds 10 micrometers, correct the lubrication.
- Symptom: Valve vibration occurs after a process change.
- Check the positioner operation.
- Measure the valve vibration.
- If vibration exceeds 4.5 mm/s, check the battery.
6. Failure Cause Matrix
| Symptom | Likely causes | Diagnostic Test | Expected result |
|---|---|---|---|
| Valve stiction |
|
|
|
7. Root Cause Analysis for each fault
7.1. Incorrect Positioner Setup
Valve flutter often occurs due to incorrect positioninger settings. The positioninger must accurately respond to the signal in order for the valve to be positioned correctly. Incorrect settings may cause severe oscillation, leading to reduced control accuracy.
To confirm the causes, check the positioner settings and measure the signal supplied to the positioner. If the signal does not match the required range (e.g., 4-20 mA), adjust the settings.
If the malfunction is not eliminated, this may lead to incorrect process control, increased energy consumption and damage to the valve.
7.2. Insufficient Battery Size
The battery must be rated for the maximum load current to ensure stable valve movement. If the battery is not powerful enough, it cannot provide the required speed and force, resulting in fluctuations.
For testing, measure the current consumed by the valve and compare it with the nominal current of the battery. If the consumed current exceeds the nominal value, the battery must be replaced.
If the fault is not eliminated, this may lead to battery overheating, battery failure, and loss of control over the valve.
7.3. Inadequate Lubrication
Insufficient lubrication of the valve rod may lead to increased friction, causing vibrations. Lubrication ensures smooth movement of the rod and prevents wear.
For testing, the friction level must be measured. If the friction exceeds 10 micrometers, the lubrication condition should be checked and adjustments made.
If the malfunction is not eliminated, this may lead to piston wear, valve damage and reduced service life.
7.4. Incompatibility with the process
Valve vibrations may be caused by incompatibility between the valve and the process. If the process parameters do not match the valve characteristics, this may cause unstable operation.
For verification, measure process parameters such as pressure, temperature, and volume. If the parameters exceed the permissible values, adjust the valve settings.
If the malfunction is not eliminated, this may lead to incorrect process control, loss of accuracy and equipment damage.
8. Step-by-step troubleshooting procedures
8.1. Incorrect Positioner Setup
- Check the positioner settings.
Use a multimeter to check the signals going to the positioner. Ensure that the signal is within the 4-20 mA range.
- Adjust settings.
Use the aligner to adjust according to technical specifications. Ensure that the aligner meets the requirements.
- Check the result.
After adjustment, the valve must stably settle in the required position without oscillations.
8.2. Insufficient Battery Size
- Measure the consumed current.
Use a multimeter to measure the current consumed by the valve. Ensure that the current does not exceed the battery rating.
- Replace the battery.
If the current exceeds the nominal value, replace the battery with a higher capacity model.
- Check the result.
After replacing the battery, the valve must operate stably without fluctuations.
8.3. Inadequate Lubrication
- Measure the friction level.
Use a vibration analyzer to measure friction. Ensure that friction does not exceed 10 micrometers.
- Check the lubrication condition.
Use a thermocamera to check the rod temperature. Ensure that the temperature does not exceed the permissible values.
- Replace the lubricant.
If the lubricant does not meet the requirements, replace it with the appropriate type.
- Check the result.
After replacing the grease, the valve must operate stably without fluctuations.
8.4. Incompatibility with the process
- Measure the process parameters.
Use a multimeter to measure pressure, temperature, and volume. Ensure that the parameters meet the requirements.
- Adjust settings.
Use the aligner to adjust settings according to process parameters.
- Check the result.
After adjustment, the valve must stably set in the required position without oscillations.
9. Preventive Measures
| Root Cause | Preventive strategy | Monitoring method | Recommended interval |
|---|---|---|---|
| Incorrect positioning controller setup | Regular inspection of settings | Multimeter, positioner | Monthly |
| Insufficient battery size | Regular current check | Multimeter | Monthly |
| Insufficient lubrication | Regular inspection of friction | Vibration Analyzer | Monthly |
| Incompatibility with the process | Regular inspection of process parameters | Multimeter | Monthly |
10. Parts and Components
| Component description | Specification | When to replace | Category UNITEC-D |
|---|---|---|---|
| Positioner | Siemens Simatic S7-1200 | After 5000 hours of operation | Category 3: Control Devices |
| Battery | 24 V, 10 A | After 5000 hours of operation | Category 3: Control Devices |
| Lubricant | Industrial grease, ISO 10684 | After 2000 hours of operation | Category 2: Lubricants |
| Rod | Steel, 10 mm | After 10000 hours of operation | Category 1: Main Components |
Для отримання додаткової інформації про запчастини, відвідайте сайт UNITEC-D: https://www.unitecd.com/e-catalog/