1. General scope and purpose
This technical support manual applies to the solenoid valve island used in industrial air line control systems. Valve island maintenance is performed during periodic maintenance or when malfunctions in the system are detected. The purpose of this manual is to ensure the safe and efficient operation of the valve island, and to identify and correct malfunctions.
2. Safety before starting work
Important: Perform a lockout/tagout (LOTO) procedure before starting service to avoid unexpected movement or energy. Use personal protective equipment (protective gloves, goggles, helmet).
Caution: High voltages or fluids may remain when working with solenoid valves. Perform maintenance only after the system is completely shut down.
3. Necessary tools and materials
| Tool / material |
Specification |
Quantity |
| Torque screw |
0–100 Nm |
1 |
| Multimeter |
0–500 V, 0–20 MΩ |
1 |
| Vacuum cleaner |
0.5–2.5 mm |
1 |
| A laser for measuring parallelism |
±0.02 mm |
1 |
| Compressor |
0–10 bar |
1 |
| Pressure manometer |
0–15 bar |
1 |
| Cleaning products |
For suction and removal of liquids |
1 |
4. Before servicing: inspection instructions
| Item |
Verification |
Acceptance / rejection criterion |
Notes |
| 1 |
Shutting down the system |
Power is completely off |
Apply LOTO |
| 2 |
No pressure |
Pressure on the manometer ≤ 0.1 bar |
Use a vacuum cleaner |
| 3 |
Lack of fluids |
There are no cleaning products |
Clean as you work |
| 4 |
Sanitary floor |
The valves are clean |
Use a vacuum cleaner |
5. Step by step procedure
- Boiler Testing
- Connect the multimeter to the boiler. Set the resistance measurement mode. The resistance of the boiler should be within 100-120 ohms.
- Measure the voltage on the boiler. The voltage should be within 230 V ± 10%. If a deviation is detected, replace the boiler module.
- Error: incorrect setting of the multimeter.
- Stem Cleaning
- Unscrew the fitting to remove the stem. Use a vacuum cleaner to remove accumulated liquids.
- Measure the distance between the ends of the rod. The distance should be 10–12 mm. If wear is found, replace the rod.
- Error: not removing fluid.
- Checking for Manifold Leaks
- Connect the vacuum cleaner to the manifold. Press the valves to create a pressure of 1-2 bar.
- Use a manometer to measure pressure. The pressure should remain stable for 5 minutes.
- Error: Incorrect installation of the sucker .
- Assembly and fixation
- Return the stem to the manifold. Use a torque screw with a range of 0-100 Nm for fixing.
- Check the distance between the rod ends. The distance should be 10–12 mm.
- Error: not using the correct torque screw.
6. After service: inspection
| Test |
Expected result |
Actual result |
Pass/Fail |
| Boiler resistance |
100–120 Ohms |
|
|
| Boiler voltage |
230 V ± 10% |
|
|
| Manifold pressure |
1–2 bar |
|
|
| The distance between the ends of the rod |
10–12 mm |
|
|
7. Technical assistance
| Symptom |
A possible reason |
Correction |
| Unstable pressure |
Manifold leak |
Check the pressure and repair the leak |
| Incorrect operation of the valve |
Worn stem |
Replace the stem |
| Incorrect resistance measurement |
Incorrect installation of the multimeter |
Check the multimeter installation |
8. Recommended maintenance schedule
| Task |
Frequency |
Estimated duration |
Skill level |
| Boiler testing |
monthly |
15 minutes |
Average |
| Cleaning the stem |
Quarterly |
30 minutes |
Average |
| Leakage check |
monthly |
20 minutes |
Average |
9. List of spare parts
| Part description |
Normal specification |
UNITEC-D category |
| Boiler module |
230 V, 100–120 Ohm |
UNITEC-D 4567 |
| stock |
10–12 mm |
UNITEC-D 1234 |
| Vacuum cleaner |
0.5–2.5 mm |
UNITEC-D 8901 |
For a complete parts list and additional information, go to https://www.unitecd.com/e-catalog/.
10. Reference books
This manual complies with DSTU 3030:2014, EN 12261, ISO 10424 and ISO 8068. Refer to the original manufacturer's documentation for additional information.