Solución de problemas de temperatura de descarga alta del compresor de tornillo

Technical analysis: Troubleshooting screw compressor high discharge temperature: oil level, cooler fouling, thermostat f

Solución de problemas de temperatura de descarga alta del compresor de tornillo

1. Descripción y alcance del problema

Rotary screw air compressors depend heavily on oil injection for lubrication, sealing, and thermal management. When the discharge temperature exceeds operational thresholds, the unit typically triggers a shutdown to protect against severe mechanical degradation. This diagnostic guide addresses high discharge temperature events (trips occurring above 105 degrees Celsius / 221 degrees Fahrenheit, with warning alarms triggering at 98 degrees Celsius / 208 degrees Fahrenheit) across oil-injected rotary screw compressors operating in automotive, aerospace, food processing, chemical, and general manufacturing facilities. Severity is classified as Critical; continued operation above 110 degrees Celsius / 230 degrees Fahrenheit leads rapidly to varnish formation, oil breakdown, thermal distortion of airend rotors, and catastrophic bearing seizure.

2. Precauciones de seguridad

DANGER: HAZARDOUS ENERGY AND STORED PRESSURE

Before initiating any diagnostic or corrective procedure on an industrial screw compressor, execute strict Lockout/Tagout (LOTO) protocols in compliance with OSHA 29 CFR 1910.147 (US) or BS EN 1037 / PUWER (UK). Verify zero mechanical, electrical, and pneumatic energy state.

  • Pneumatic Stored Energy: Isolate the compressor from the plant air header via a lockable ball valve. Verify zero pressure on the air-oil receiver tank pressure gauge before opening any lines. Residual pressure causes sudden fluid expulsion.
  • Thermal Hazards: Discharge piping, oil coolers, airends, and separator vessels operate at extreme temperatures (80 degrees Celsius to 115 degrees Celsius / 176 degrees Fahrenheit to 239 degrees Fahrenheit). Wear heavy insulating leather gloves and safety glasses with side shields (ANSI Z87.1 / EN 166).
  • Electrical Hazards: Voltage up to 690V AC may be present in the starter cabinet. Use a calibrated multimeter to verify zero voltage before inspecting control wiring or temperature RTDs.
  • Personal Protective Equipment (PPE): Flame-retardant coveralls, steel-toe footwear, and hearing protection if operating adjacent to running machinery.

3. Herramientas de diagnóstico necesarias

Nombre de la herramienta Especificación/modelo Rango de medición Objetivo
Multímetro digital (DMM) CAT III 1000 V/CAT IV 600 V (p. ej., Fluke 87 V) 0 – 1000V AC/DC, 0 – 50Mohm, 0 – 400mA Check RTD/thermocouple resistance and control circuit voltage.
Cámara termográfica infrarroja Resolution 160×120 pixels min. (e.g., Fluke Ti401PRO) -20 degrees Celsius to +500 degrees Celsius Scan oil cooler tubes, thermal valve housing, and discharge piping for thermal differentials.
Analizador de vibraciones FFT capable, 3-axis accelerometer 10 Hz – 10 kHz, 0.1 – 50 mm/s Evaluate airend and motor bearing health during diagnostic run.
Manómetro / Manómetro de Presión Diferencial Digital differential manometers 0 – 7 bar / 0 – 100 psi Measure pressure drop across air/oil separators and oil filters.
Anemómetro / Medidor de velocidad del aire Vane or hot-wire anemometer 0.2 – 25 m/s Verify enclosure and room ventilation airflow rates.

4. Lista de verificación de evaluación inicial

Parámetro / Observación Rango de funcionamiento normal Abnormal Indicator Acción / Registro
Ambient Room Temperature +5 degrees Celsius to +40 degrees Celsius > 40 degrees Celsius (104 degrees Fahrenheit) Record exact room temp; check ventilation louvers and exhaust fans.
Operating Discharge Pressure 7.0 bar to 10.0 bar (100 – 145 psi) Running above rated maximum pressure Check plant demand, pressure switch setpoints, and regulator.
Sump Oil Level (Sight Glass) 1/2 to 3/4 full with system stopped/depressurized Below 1/4 or completely opaque/foaming Inspect for oil leaks; note if oil is degraded or contaminated.
Compressor Load Duty Cycle Modulating or Load/Unload (70-90% load) Continuous 100% load with high ambient load Review SCADA/PLC history for recent load profile changes.
Error Log History No prior thermal faults in last 500 hours Recurring warning codes (A04, E12, etc.) Download PLC fault log with timestamps and operating hours.

5. Diagrama de flujo del diagnóstico sistemático

Follow this decision tree systematically from top to bottom. Do not skip steps.

  1. Initial Symptom Verification
    • IF compressor tripped on high discharge temperature (> 105 degrees Celsius):
    • Allow unit to cool to < 40 degrees Celsius before opening panels.
    • Check oil level via receiver sight glass.
      • IF oil level is low: Proceed to Root Cause 1 (Low Oil Level).
      • IF oil level is normal/correct: Proceed to step 2.
  2. Thermal Differential & Cooler Inspection
    • Start compressor in unloaded state or monitor immediately upon startup (if safe).
      • Using thermal imager, scan the oil cooler inlet and outlet lines.
      • IF temperature drop across the oil cooler is less than 8 degrees Celsius (Delta-T < 8 degrees Celsius): Proceed to Root Cause 2 (Cooler Fouling / Blockage).
      • IF temperature drop across the cooler is normal (> 15 degrees Celsius) but oil entering the airend remains hot: Proceed to step 3.
  3. Thermal Bypass Valve Verification
    • Measure temperature of the oil line returning from the cooler versus the bypass line entering the thermostatic valve housing using an infrared thermometer.
      • IF the bypass line remains hot when discharge temperature exceeds opening threshold (typically 60-75 degrees Celsius): Proceed to Root Cause 3 (Thermostatic Valve Failure).
      • IF thermostatic valve operates correctly: Proceed to step 4.
  4. Environmental & Ventilation Assessment
    • Measure ambient temperature at compressor intake and room exhaust.
      • IF ambient temperature > 40 degrees Celsius or ventilation airflow is restricted: Proceed to Root Cause 4 (Adverse Ambient Conditions / Ventilation Failure).
      • IF ambient conditions are within spec: Proceed to Root Cause 5 (Sensor Calibration / Electrical Fault).

6. Matriz de causa de falla

Síntoma Causas probables (clasificadas) Prueba de Diagnóstico Resultado esperado si se confirma la causa
Discharge temp reaches 108 degrees Celsius within 15 mins of load. 1. Thermostatic valve stuck closed
2. Low oil level
3. Blocked oil cooler fins
Thermal imaging of valve housing and cooler lines; sight glass check. Bypass line hot, cooler inlet cold; low sight glass; uneven thermal gradient on cooler.
Gradual temperature increase over 2-3 months of operation. 1. External dust/debris on cooler fins
2. Internal oil varnish/sludge
3. Degraded compressor oil
Visual inspection of cooler core; oil sample analysis (ASTM D445 viscosity). Fins caked with particulate; high oil acid number (TAN) and elevated viscosity.
Instantaneous high temp trip on startup with cold pipes. 1. RTD sensor failure / short circuit
2. Loose sensor wiring terminal
Measure RTD resistance (Pt100/Pt1000) with DMM at terminal block. Resistance reading does not match actual ambient temperature curve.
High temp trip only during afternoon peak shift hours. 1. Room exhaust fan failure
2. Ducting static pressure restriction
3. High ambient temperature
Anemometer airflow measurement; room temperature logger review. Airflow below OEM spec (m3/h); room temp exceeding 40 degrees Celsius.

7. Análisis de la causa raíz de cada falla

Root Cause 1: Low Oil Level

Explanation: Compressor oil serves a triple function: lubrication, sealing of rotor clearances, and direct heat absorption from the compression chamber. When the oil charge drops below the minimum operating threshold, the smaller volume of oil absorbs the same mechanical and thermodynamic heat load, resulting in a rapid temperature spike. Low oil levels also reduce the oil flow rate through the thermostatic valve and oil cooler, accelerating thermal degradation.

Confirmation: Check the oil receiver sight glass with the compressor shut down and depressurized. If the level is below the minimum mark, or if oil consumption exceeds 0.05% of total mass flow rate, check for external leaks at shaft seals, oil filter gaskets, separator elements, and oil cooler headers.

Consequences: Severe oil starvation leads to direct metal-to-metal contact between male and female rotor lobes, scoring of airend housing bores, rapid bearing cage failure, and total airend seizure requiring complete replacement.

Root Cause 2: Oil Cooler Fouling (External & Internal)

Explanation: Rotary screw compressors utilize air-cooled or water-cooled heat exchangers. External fouling occurs when airborne particulates (dust, lint, paper, chemical mist) are drawn across the aluminum or copper fin pack by the cooling fan, forming an insulating blanket that blocks convective heat transfer. Internal fouling occurs due to carbonization, varnish, and oil oxidation products lining the inner tube walls, restricting thermal conductivity.

Confirmation: Use a thermal imager across the cooler matrix. A fouled cooler exhibits a high temperature differential (Delta-T) across the core face without a corresponding drop in oil temperature, or shows localized cold/hot spots indicating blocked tubes.

Consequences: Reduced heat rejection forces the circulating oil to enter the airend at elevated temperatures (e.g., 70 degrees Celsius instead of 55 degrees Celsius), compounding the compression heat and triggering high-temperature shutdowns.

Root Cause 3: Thermostatic Mixing Valve Failure

Explanation: The thermostatic valve directs compressor oil either directly back to the airend (during cold startup to accelerate warm-up) or through the oil cooler (once normal operating temperature is reached). The internal wax element degrades over time, losing expansion capability, or the sliding spool sticks due to varnish accumulation.

Confirmation: Monitor the oil lines connected to the thermostatic valve body using an infrared thermometer. If the line leading to the oil cooler remains cool while the discharge temperature exceeds 90 degrees Celsius, the valve element is stuck closed, recirculating hot oil directly back into the airend.

Consequences: Total bypass of the cooling circuit prevents heat rejection, causing the oil temperature to escalate exponentially within minutes of loading.

Root Cause 4: Adverse Ambient Conditions & Ventilation Failure

Explanation: Air-cooled compressors reject total electrical and mechanical input energy as heat into the equipment room. If room ventilation capacity (exhaust fan CFM) is inadequate, or if ambient temperatures exceed 40 degrees Celsius (104 degrees Fahrenheit), the temperature differential between the cooling medium (ambient air) and the hot oil diminishes, reducing heat transfer efficiency.

Confirmation: Measure ambient temperature within 1 meter of the compressor air intake using a calibrated thermocouple. Check auxiliary exhaust fan rotation, drive belt tension, and ductwork backpressure.

Consequences: Chronic high operating temperatures shorten compressor lubricant life by 50% for every 10 degrees Celsius rise above 80 degrees Celsius, accelerating additive depletion and varnish formation.

Root Cause 5: Temperature Sensor (RTD / Thermocouple) Calibration Drift

Explanation: Platinum resistance temperature detectors (Pt100 or Pt1000) or thermocouple probes degrade due to vibration, thermal cycling, or moisture ingress, causing them to report artificially high temperature readings to the PLC/controller.

Confirmation: Disconnect the RTD from the controller and measure resistance directly with a DMM. Compare the measured resistance to the standard ITS-90 RTD resistance table (e.g., 100 ohms at 0 degrees Celsius, 138.51 ohms at 100 degrees Celsius). Alternatively, verify sensor tip temperature using a calibrated surface probe pyrometer.

Consequences: Nuisance tripping interrupts production even when actual internal temperatures are normal, leading to operator workarounds or unnecessary hardware replacement.

8. Procedimientos de resolución paso a paso

Resolution 1: Correcting Low Oil Level & Replenishing Fluid

  1. Execute full LOTO on the compressor electrical supply and bleed all air pressure from the receiver tank to 0.0 bar / 0 psi.
  2. Inspect all joints, hoses, shaft seals, and oil filter spin-on gaskets for signs of leakage. Repair or replace compromised fittings.
  3. Remove the oil fill plug slowly to ensure no residual trapped pressure exists.
  4. Pump or pour OEM-specified synthetic compressor lubricant (ISO VG 46 or 68 depending on ambient spec) into the receiver tank until the fluid level reaches the 3/4 mark on the sight glass with the system settled.
  5. Secure the fill plug with a calibrated torque wrench to the manufacturer’s specified torque (typically 45-60 Nm).
  6. Clear LOTO, restart the compressor in unload mode for 5 minutes, check for leaks, then load the unit and monitor discharge temperature stabilization (Target: 78 – 85 degrees Celsius).

Resolution 2: Cleaning and Flushing the Oil Cooler

  1. Execute LOTO on electrical and pneumatic energy sources.
  2. Allow the cooler core to cool below 40 degrees Celsius (104 degrees Fahrenheit).
  3. External Cleaning: Using compressed air (regulated to < 2.0 bar / 30 psi) or a soft-bristle brush, blow out dust and debris from the cooling fins in the reverse direction of normal airflow. For greasy residue, apply an industrial alkaline biodegradable coil cleaner, allow 10 minutes dwell time, and rinse gently with low-pressure water, ensuring electrical components are fully shrouded.
  4. Internal Flushing (if oil-side fouled): Disconnect oil lines from the cooler inlet and outlet manifolds. Circulate a specialized varnish-removal solvent or flushing oil through the core using an external pump rig for 2 to 4 hours in accordance with ASTM standards. Flush thoroughly with clean compressor oil before reassembly.
  5. Re-torque all hydraulic line fittings to correct standards (e.g., JIC flare or DIN fittings per ISO 8434-1).
  6. Restart and verify Delta-T across the cooler exceeds 12 degrees Celsius under full load.

Resolution 3: Replacing the Thermostatic Mixing Valve Element

  1. Execute LOTO and depressurize the compressor system completely.
  2. Drain oil from the thermostatic valve housing down to a level below the valve cover.
  3. Remove the retaining bolts on the thermostatic valve cover plate and lift off the cover. Extract the O-ring seal and the wax element assembly.
  4. Inspect the internal bore for varnish or scoring. Clean the housing bore with fine emery cloth (600 grit) and solvent cleaner.
  5. Install a new thermostatic element kit (ensuring the correct nominal temperature rating, e.g., 71 degrees Celsius / 160 degrees Fahrenheit nominal start-to-open). Fit a new O-ring seal lubricated with clean compressor oil.
  6. Bolt down the cover evenly in a cross-pattern to 25 Nm torque.
  7. Top off the oil level, clear LOTO, and test compressor warm-up cycle. Verify that oil flows to the cooler once discharge temperature reaches the valve setpoint.

Resolution 4: Remediating Ventilation and Ambient Conditions

  1. Verify compressor room exhaust fan electrical supply, rotation direction, and belt tension. Clean intake louvers and removable pre-filters.
  2. If room ambient temperature exceeds 40 degrees Celsius, install auxiliary ducted fresh air supply fans drawing from outside the building envelope, sized to meet total heat rejection requirements (typically 3.5 m3/min per kW of compressor motor power per CAGI/Pneurop guidelines).
  3. Ensure hot air discharge ducting from the compressor enclosure has zero static pressure restriction and discharges directly outdoors without recirculation.
  4. Verify motor current draw with a clamp meter to ensure cooling fans are not overloaded.

Resolution 5: Replacing and Calibrating Temperature Sensors

  1. Execute LOTO on the electrical supply. Open the control panel.
  2. Disconnect the Pt100/Pt1000 RTD sensor leads from the analog input module.
  3. Unscrew the sensor probe from the discharge manifold thermowell.
  4. Test the removed sensor in a calibrated dry-block calibrator or ice bath (0 degrees Celsius) and boiling water (100 degrees Celsius) using a DMM. If resistance deviates more than +/- 0.5% from the ITS-90 reference table, discard the sensor.
  5. Install a new replacement RTD sensor with thread sealant suitable for high-temperature service (rated to 150 degrees Celsius). Torque to 15 Nm.
  6. Reconnect wiring to the PLC terminal block, verify loop integrity, and perform a live read check via the compressor human-machine interface (HMI).

9. Medidas preventivas

Causa raíz Estrategia de Prevención Método de seguimiento Intervalo recomendado
Low Oil Level Establish daily pre-start inspection routine; monitor daily oil makeup volume. Daily visual check of receiver sight glass; low-level alarm interlock verification. Diariamente / Cada 8 horas de funcionamiento
Incrustaciones más frías Install intake pre-filters on compressor room louvers; schedule cleanings based on dust load. Monthly thermal imaging of cooler matrix; differential pressure monitoring across air-side core. Monthly cleaning; Quarterly thermal audit
Fallo de la válvula termostática Prevent oil oxidation by adhering to strict oil change intervals (synthetic polyolester / PAO oils). Scheduled oil sample analysis (Spectrochemical wear metals, TAN, viscosity). Every 2,000 hours or Annually (oil analysis every 1,000 hours)
Ventilation Failure Maintain room cooling fans and clean louvers; enforce maximum ambient temp limits (< 40 degrees Celsius). Ambient room temperature datalogger installed near compressor intake. Bi-annual inspection and filter replacement
Sensor Calibration Drift Use industrial-grade RTDs with vibration-resistant potting; periodic calibration check. Compare HMI temperature readout against calibrated infrared pyrometer gun. Annually during scheduled plant shutdown

10. Repuestos y componentes

Descripción de la pieza Especificación Cuando reemplazar Categoría UNITEC
Thermostatic Valve Element Kit 71 degrees Celsius / 160 degrees Fahrenheit rating, brass/wax core with Viton O-rings Every 8,000 operating hours or upon sticking failure Thermal Management / Compressor Spares
Pt100 RTD Temperature Sensor Class A, 3-wire, 1/4″ NPT thread, -50 to +200 degrees Celsius When calibration drift exceeds +/- 1.5 degrees Celsius Instrumentation & Control
Lubricante sintético para compresores ISO VG 46 / PAO-ester blend, food-grade or industrial grade Every 4,000 to 8,000 hours (oil analysis dependent) Fluids & Lubricants
Elemento separador de aire/aceite Coalescing media with grounding stapling, max 0.2 bar initial dP Every 4,000 operating hours or when dP exceeds 0.8 bar Elementos de filtración
Spin-on Oil Filter Element 10-micron filtration rating, 15 bar burst pressure, internal bypass valve Every 2,000 operating hours with scheduled oil changes Elementos de filtración

To source OEM-equivalent replacement parts, thermostatic kits, sensors, and lubricants engineered for industrial rotary screw compressors, explore the UNITEC-D E-Catalog.

11. Referencias

  • ANSI / CAGI – Performance Standard for Rotary Screw Compressors.
  • ASME Boiler and Pressure Vessel Code (BPVC) – Section VIII, Division 1 (Compressed Air Receivers).
  • OSHA 29 CFR 1910.147 – The Control of Hazardous Energy (Lockout/Tagout).
  • BS EN 1037 / PUWER 1998 – Safety of Machinery – Prevention of Unexpected Start-up (UK).
  • IEEE 43 – Recommended Practice for Testing Insulation Resistance of Rotating Machinery.
  • UNITEC-D Maintenance Engineering Bulletin: Rotary Screw Thermal Management Best Practices (Doc REF: UDM-TR-049).

Related Articles

Solución de problemas de temperatura de descarga alta del compresor de tornillo

Technical analysis: Troubleshooting screw compressor high discharge temperature: oil level, cooler fouling, thermostat f

Solución de problemas de temperatura de descarga alta del compresor de tornillo
This guide provides a systematic approach for diagnosing high discharge temperature in screw compressors, covering oil level, cooler fouling, thermostat failure, and ambient conditions. Technicians wi

1. Descripción y alcance del problema

La alta temperatura de descarga (HDT) en los compresores de tornillo rotativo es un indicador crítico de la ineficiencia del sistema, la degradación de los componentes y posibles fallas catastróficas. Esta guía aborda los compresores de tornillo enfriados por aire y por agua que funcionan en entornos industriales. HDT se define como temperaturas de funcionamiento que exceden el umbral de descarga recomendado por el fabricante, lo que generalmente resulta en el apagado automático de la máquina para proteger la unidad compresora. Si no se soluciona esta condición, se producirá una rápida oxidación del aceite, fallas en los cojinetes y desgaste mecánico prematuro.

Clasificación de gravedad: Crítico. El funcionamiento continuo por encima de 105 °C (221 °F) compromete la integridad del aceite y acorta la vida útil de los componentes en un 50 % por cada aumento de 10 °C por encima de los límites operativos normales.

2. Precauciones de seguridad

ADVERTENCIA: LOS SISTEMAS COMPRESORES CONTIENEN ENERGÍA ALMACENADA. ANTES DE REALIZAR CUALQUIER TAREA DE DIAGNÓSTICO O MANTENIMIENTO, REALICE PROCEDIMIENTOS COMPLETOS DE BLOQUEO/ETIQUETADO (LOTO). AISLAR EL COMPRESOR DE LA ENERGÍA ELÉCTRICA, VENTAR TODA LA PRESIÓN DEL AIRE A LA ATMÓSFERA Y PERMITIR QUE EL SISTEMA SE ENFRÍE POR DEBAJO DE 40°C (104°F) PARA EVITAR QUEMADURAS TÉRMICAS. UTILICE EPP APROPIADO, INCLUYENDO GUANTES CON AISLAMIENTO TÉRMICO, GAFAS DE SEGURIDAD Y BOTAS CON PUNTERA DE ACERO.

3. Herramientas de diagnóstico necesarias

Nombre de la herramientaEspecificación/modeloRango de mediciónPropósito
Cámara infrarrojaSensibilidad térmica < 0,05°C-20°C a 500°CIdentificación de obstrucciones del refrigerador y detección de puntos calientes
Termopar digitalTipo K, precisión clase 1-50°C a 1200°CVerificación de las temperaturas del aire y del aceite de descarga.
AnemómetroTipo paleta o hilo caliente0 a 20 m/sMedición del flujo de aire de refrigeración a través del gabinete
Manómetro diferencialescala de 0-2 barras0 a 2 barrasPrueba de caída de presión del filtro de aceite y del enfriador

4. Lista de verificación de evaluación inicial

Comprobar artículoacciónUmbral/Nota
Nivel de aceiteVerifique el nivel de aceite en la mirilla bajo cargaDebe estar dentro del rango operativo
Condiciones ambientalesRegistrar la temperatura ambiente del aire de entradaObjetivo: < 35°C (95°F)
Horas de funcionamientoVerifique el controlador para conocer la fecha del último mantenimientoComparar con el intervalo de servicio
Historial de alarmasRevise el registro del controlador para conocer la frecuencia de HDT¿Es esto repentino o gradual?

5. Diagrama de flujo del diagnóstico sistemático

  1. Síntoma: Alarma de temperatura de descarga alta
    • Paso 1: Verificar la temperatura real. Utilice un termopar digital calibrado en la tubería de descarga. Si la lectura del sensor es significativamente diferente de la lectura del medidor, el sensor de temperatura está defectuoso.
    • Paso 2: Verifique el ambiente y la ventilación. Verifique la temperatura ambiente. ¿Está restringida la entrada de aire? Si la temperatura ambiente es > 40°C, el sistema se sobrecalentará.
    • Paso 3: Analizar el enfriador de aceite. Utilice la cámara infrarroja para verificar si hay puntos fríos en las aletas del radiador.
      • Si existen puntos fríos, el enfriador está sucio (interna o externamente).
      • Si todo el enfriador está caliente, el aceite no está pasando por alto o el termostato está atascado.
    • Paso 4: Verificar el funcionamiento del termostato de aceite. Verifique la temperatura de la línea de aceite que conduce al enfriador. Si la línea permanece fría a pesar de la alta temperatura de descarga, el termostato falla en la posición de derivación.

6. Matriz de causa de falla

SíntomaCausa probablePrueba de DiagnósticoResultado esperado
HDT + nivel bajo de aceiteConsumo/fuga de aceiteInspección visual de la mirilla.Nivel por debajo del indicador mínimo
HDT + ΔT alto en el refrigeradorEnsuciamiento del refrigerador externoInspección de cámara infrarrojaImportante gradiente de temperatura entre las aletas
HDT + ΔT bajo en refrigeradorTermostato defectuoso (cerrado)Prueba táctil de la manguera de entrada del enfriador.La manguera permanece fría bajo carga
HDT + ambiente altoFallo de ventilaciónTermómetro ambientalTemperatura ambiente > 40°C

7. Análisis de la causa raíz de cada falla

7.1 Nivel y calidad del aceite

El aceite sirve como lubricante y refrigerante en los compresores de tornillo. Los niveles bajos de aceite reducen el volumen de fluido de transferencia de calor, lo que provoca una sobrecarga térmica. Además, la descomposición del aceite (lodos/barniz) aumenta la fricción y restringe la transferencia de calor.

7.2 Incrustaciones más frías

La contaminación externa ocurre cuando los filtros de entrada fallan, lo que permite que el polvo y los desechos obstruyan las aletas del radiador, lo que reduce la eficiencia del intercambio de calor. La contaminación interna ocurre cuando los productos de degradación del aceite se depositan dentro de los tubos del radiador, creando una barrera térmica.

7.3 Falla del termostato

El termostato de aceite regula el flujo de aceite al enfriador. Si falla en la posición cerrada (bypass), el aceite caliente regresa directamente al compresor sin pasar por el enfriador. Esto da como resultado un aumento inmediato de temperatura bajo carga.

7.4 Condiciones ambientales

Los compresores de tornillo están diseñados para funcionar dentro de límites específicos de temperatura ambiente. Las altas temperaturas ambiente reducen el ΔT disponible para la transferencia de calor, lo que obliga al compresor a funcionar más caliente.

8. Procedimientos de resolución paso a paso

8.1 Resolución del nivel bajo de aceite

  1. Realizar LOTO.
  2. Deje que el sistema se despresurice por completo.
  3. Inspeccione si hay fugas (accesorios, mangueras, sello de aceite).
  4. Agregue lubricante aprobado por el fabricante al nivel apropiado.
  5. Verifique el estado del filtro de aceite (si está restringido, se impide el flujo de aceite).

8.2 Resolución de incrustaciones en el refrigerador

  1. Realizar LOTO.
  2. Externo: Utilice aire comprimido (por debajo de 2 bar) o una solución de detergente suave para limpiar el paquete de aletas. No utilices limpiadores a presión ya que pueden colapsar las aletas.
  3. Interno: si se sospecha, lave el sistema de enfriamiento usando un solvente de enjuague con aceite recomendado según el boletín técnico del fabricante.

8.3 Resolución de fallas del termostato

  1. Realizar LOTO.
  2. Ubique la carcasa del termostato (generalmente cerca del compresor).
  3. Retire la tapa de la carcasa y extraiga el elemento termostático.
  4. Pruebe el elemento en un baño de agua caliente (debe abrirse a la temperatura nominal, normalmente entre 70 y 80 °C).
  5. Reemplace con un elemento nuevo y una junta nueva. Apriete según las especificaciones de torsión.

9. Medidas preventivas

Causa raízEstrategia de PrevenciónMétodo de seguimientoIntervalo recomendado
Nivel de aceiteComprobación de nivel diariaVerificación de mirillaDiariamente
Incrustaciones más fríasFiltración de aire de admisiónMonitoreo de presión diferencialMensual
TermostatoAnálisis de aceite periódicoPrueba de rendimiento anualAnualmente
ambienteOptimización de la ventilaciónSensor de temperatura ambienteContinuo

10. Repuestos y componentes

Descripción de la piezaEspecificaciónCuando reemplazarCategoría UNITEC
Elemento del termostato de aceiteEspecífico del OEMCada 8.000 horas de funcionamientoRepuestos para compresores
Filtro de aceiteFlujo total, 10 micronesCada 2.000-4.000 horasKits de mantenimiento
Conjunto de enfriadorEspecífico del OEMSi la contaminación interna no es recuperableComponente principal

Para todas las piezas de repuesto, consulte el catálogo electrónico de UNITEC-D: https://www.unitecd.com/e-catalog/

11. Referencias

  • ASME PTC 9: Código de prueba de rendimiento para compresores
  • ANSI/CAGI B19.1: Norma de seguridad para sistemas de aire comprimido
  • Manuales de servicio técnico OEM para lubricación y control térmico

Related Articles