This manual is intended for the maintenance of compressed air preparation units (FRL - Filter-Regulator-Lubricator) in industrial pneumatic systems. Covers the following operations:
Replacement of filter elements (coalescent and dust filters)
Inspection and replacement of pressure regulator diaphragms
Refueling and adjustment of the lubricator
Cleaning and checking the tightness of nodes
Maintenance is carried out in accordance with DSTU EN ISO 8573-1:2016 (purity of compressed air) and DSTU EN 983:2015 (safety requirements for pneumatic systems). The recommended frequency is every 2000 hours of operation or once every 6 months (depending on operating conditions).
Safety Precautions
ATTENTION! BEFORE STARTING WORK:
Turn off the power to the compressor and de-energize the pneumatic system. Perform the Lockout/Tagout procedure according to DSTU EN 1037:2015.
Relieve the residual pressure in the system. Open the drain valve until the air has completely stopped escaping (minimum 30 seconds). The pressure in the system should be 0 bar.
Use personal protective equipment (PPE): safety glasses (EN 166), gloves (EN 388), safety shoes (EN ISO 20345).
Do not allow grease to fall on the floor - use a tray to collect the used liquid.
Work in a well-ventilated area. Lubricant vapors can cause respiratory tract irritation.
Tools & Materials Required
Tool/Material
Specification
Quantity
Dynamometric key
Range 5–50 Nm, accuracy class ±3%
1
The screwdriver is insulated
PH2 slot, insulation up to 1000 V (EN 60900)
1
Horn key
Size 17mm, 19mm, 22mm
1 set
Control manometer
Range 0–10 bar, accuracy class ±0.5%
1
Vernier caliper
Digital, range 0-150mm, accuracy ±0.02mm
1
Pneumatic leak detector
Sensitivity 1×10-6 mbar·l/s
1
Lubricant for pneumatics
ISO VG 32 or ISO VG 46 (according to DSTU ISO 3448:2015) such as Mobil DTE 24
500 ml
Filter element
Coalescent filter, class 1 μm (according to ISO 8573-1)
1
Diaphragm regulator
Nitrile rubber (NBR), diameter 40–60 mm (depending on the model)
1
Sealing gaskets
Silicone or fluororubber (FKM), thickness 1.5 mm
2–4 pcs.
Lint-free rags
For cleaning surfaces
5 pcs.
Spray for cleaning
No residue like CRC Contact Cleaner
1 balloon
Pre-Maintenance Inspection Checklist
Item
Verification
Acceptance/rejection criteria
Notes
1. Pressure in the system
Check the pressure gauge at the FRL outlet
The pressure should be 0 bar. If >0.5 bar – the system is not de-energized.
Use a control manometer for verification.
2. State of the filter element
Visual inspection and pressure drop check
Pressure drop > 0.5 bar or visible contamination - replacement is mandatory.
For coalescent filters - the presence of an oil film on the surface.
3. Airtightness of connections
Checking with a leak detector or soap solution
The presence of bubbles is a leak. 0 bubbles allowed in 10 seconds.
Pay special attention to threaded connections and seals.
4. Operation of the pressure regulator
Turn the adjusting screw by ±1 turn
The pressure should change smoothly, without jumps. If jumps > 0.2 bar – the diaphragm is damaged.
Check for cracks on the regulator housing.
5. Lubrication level in the lubricator
The inspection is visual through the sight glass
Level below 50% - refueling required. If the lubricant is dark/dirty, replace it.
Use only the recommended type of lubricant.
6. Condition of the drain valve
Manual opening/closing check
The valve should open freely, without jamming. The presence of corrosion - replacement.
Clean the valve from dirt before checking.
7. Electrical connections (if any)
Inspection of insulation and fastening
Insulation resistance > 1 MΩ (measure with a megohmmeter at 500 V). The presence of oxidation - clean.
Only for FRL with electronic control.
Step-by-Step Procedure
1. Dismantling the filter element
Remove the filter cover.
Unscrew the cover fastening bolts (tightening torque 12–15 Nm). Use a torque wrench.
Remove the cover carefully - there may be residual condensate inside.
Avoid dropping the lid - it may damage the seal.
Pull out the filter element.
Pull the element vertically upwards. If stuck, gently shake from side to side.
Inspect the element for mechanical damage (cracks, deformations).
Do not use metal tools for extraction - it can damage the filter housing.
Clean the filter housing.
Remove condensation and dirt from the housing with a lint-free cloth.
Wipe the sealing surface with a cleaning spray. Make sure there are no scratches or corrosion.
Check the condition of the sealing ring - if there are cracks or deformations, replace it.
2. Replacement of the diaphragm of the pressure regulator
Dismantle the pressure regulator.
Unscrew the regulator from the FRL housing (tightening torque 20–25 Nm).
Remove the adjusting screw and spring. Place them in a clean tray.
Do not lose small parts (washers, seals).
Pull out the diaphragm.
Remove the upper cover of the regulator (bolts 8–10 Nm).
Gently pull out the diaphragm. Check it for cracks, breaks or deformations.
Measure the thickness of the diaphragm with a caliper - it should be 1.0-1.2 mm. If less, replacement is mandatory.
Install the new diaphragm.
Grease the new diaphragm with a thin layer of grease (ISO VG 32).
Place the diaphragm in place, making sure it is flush in the slot.
Tighten the top cover (torque 8–10 Nm).
Do not overtighten the bolts - it can damage the diaphragm.
Assemble the regulator.
Install the spring and adjusting screw.
Attach the regulator to the FRL housing (torque 20–25 Nm).
Adjust pressure to 6 bar (or according to system requirements).
3. Refilling the lubricant
Drain the used lubricant.
Place a tray under the oiler drain valve.
Open the valve and drain all the oil. Close the valve after draining.
Do not allow grease to fall on the floor - use a pallet.
Clean the lubricator.
Fill the lubricator with cleaning spray and shake.
Drain the liquid through the drain valve.
Repeat the procedure until complete cleaning.
Fill in fresh lubricant.
Fill the lubricant up to the level of 75% (by sight glass).
Use only the recommended lubricant (ISO VG 32/46).
Close the lubricator cover (torque 5–7 Nm).
Adjust the oil flow.
Turn the oiler adjustment screw 1/4 turn clockwise (minimum flow).
Connect the system and check for oil at the outlet (visually or using a paper filter).
Gradually increase the flow until the optimal level is reached (usually 1 drop per 10 m³ of air).
4. Assembly and verification of FRL
Install a new filter element.
Insert the element into the filter housing, ensuring the correct orientation (the arrow on the element should point down).
Install the filter cover and tighten the bolts (torque 12–15 Nm).
Check for tightness.
Connect a control pressure gauge to the FRL outlet.
Apply compressed air at a pressure of 7 bar.
Apply a soapy solution to all connections. The presence of bubbles is a leak.
If there is a leak, tighten the connection or replace the seal.
Adjust the pressure.
Set the outlet pressure 6±0.2 bar using the adjusting screw.
Check the stability of the pressure - fluctuations should not exceed ±0.1 bar.
Check the operation of the lubricator.
Start the system and make sure that the lubricant reaches the outlet.
Adjust oil flow as needed.
Post-Maintenance Verification Checklist
Check
Expected result
Actual result
Passport/No passport
Airtightness of all connections
No leaks (0 bubbles in 10 s)
FRL outlet pressure
6±0.2 bar (or according to requirements)
Pressure stability
Fluctuations ≤ ±0.1 bar
Operation of the lubricator
Lubricant flows to the outlet (1 drop/10 m³)
Operation of the drain valve
The valve opens/closes freely, without leaks
Pressure drop across the filter
≤ 0.3 bar (for a new element)
Absence of extraneous noises
No whistling, knocking or vibration
Troubleshooting Guide
Symptom
Probable cause
Corrective action
Outlet pressure below normal
Damaged regulator diaphragm
Dirty filter element
Leakage in joints
Replace the diaphragm
Replace the filter element
Check for leaks and tighten the connections
Outlet pressure is higher than normal
Jamming of the adjusting screw
Damage to the regulator spring
Disassemble the regulator, clean and lubricate the screw
Replace the spring
Air leaks from the regulator
Damaged diaphragm seal
A crack in the regulator housing
Replace the seal
Replace the housing or the entire regulator
Grease does not reach the outlet
Contaminated lubricant dispenser
Low oil level
Clogging of the oil line
Clean the dispenser
Add oil
Clean the oil line
Increased pressure drop across the filter
Contaminated filter element
Incorrectly installed item
Replace the element
Check that the installation is correct
Extraneous noises (whistling, knocking)
Damage to the bearings of the lubricator
Vibration due to loose mounting
Replace the lubricant
Check and tighten fasteners
Recommended Maintenance Schedule
Task
Periodicity
Estimated completion time
Qualification level
Pressure and tightness test
Every month
15 minutes
Technician
Cleaning the drain valve
Every 3 months
20 minutes
Technician
Replacement of the filter element
Every 2000 hours or 6 months
45 minutes
Qualified technician
Replacement of the regulator diaphragm
Every 4000 hours or 12 months
60 minutes
Qualified technician
Refilling/replacing the lubricant in the lubricator