1. Description of the Problem and Scope of Application
This manual describes in detail the diagnostic and troubleshooting procedures associated with abnormally high discharge temperatures in screw compressors. A high discharge temperature is a critical indicator that can indicate a number of potentially serious problems that, if ignored, will lead to premature component wear, compressor failure, and significant repair costs.
Application: The manual is relevant for all types of oil-filled screw compressors used in industrial production, including air-cooled and water-cooled compressors.
Symptoms:
- High discharge temperature indication on the compressor control panel.
- Overheating alarm activation.
- Automatic shutdown of the compressor due to high temperature.
- The smell of overheated grease.
- Reduction of compressor efficiency.
Severity classification:
- Critical: The discharge temperature exceeds the cut-out threshold (typically 110-120 °C), causing the compressor to stop immediately. Requires immediate diagnosis and elimination.
- Significant: The discharge temperature is consistently above the operating range (eg > 100 °C with a normal range of 70-95 °C), but does not reach the trip point. This leads to accelerated degradation of the lubricant and wear of components, requiring operative intervention.
- Minor: The discharge temperature is only intermittent or slightly higher than normal. Requires monitoring and preventive measures.
2. Precautions
BEFORE BEGINNING ANY DIAGNOSTIC OR REPAIR WORK ON THE COMPRESSOR, THE FOLLOWING SAFETY PRECAUTIONS MUST BE PERFORMED TO PREVENT INJURY AND EQUIPMENT DAMAGE:
- LABEL LOCKOUT / HANGING OUT (LOTO): Before opening any panels or accessing internal components, MUST disconnect the compressor from the mains and apply the LOTO procedure in accordance with DSTU EN 1037 and internal company standards. Make sure there is no voltage.
- STORED ENERGY: Screw compressors contain a significant amount of stored energy in the form of compressed air and hot oil. Make sure the system is completely depressurized and the pressure is reduced to atmospheric. Use pressure relief valves.
- HOT SURFACES AND OILS: Compressor and oil operating temperatures can reach over 90°C. Allow the equipment to cool before operating. Use appropriate personal protective equipment (PPE).
- PERSONAL PROTECTIVE EQUIPMENT (PPE): Always use protective glasses, protective gloves (heat resistant, oil resistant), protective clothing and protective shoes.
- CHEMICALS: Compressor oil is a chemical. Avoid contact with skin and eyes. In case of contact, immediately flush the affected area with water.
- MECHANICAL MOVING PARTS: Always be careful of moving parts of the compressor (fan, rotors), even if the power is disconnected, there is a risk of accidental starting or residual rotation.
3. Necessary Diagnostic Tools
For accurate diagnosis, it is recommended to have the following tools:
| Name of the Tool | Specification/Model | Measurement range | Purpose |
|---|---|---|---|
| Digital multimeter | Class True RMS, CAT III 1000V (e.g. Fluke 179) | Voltage: 0-1000V AC/DC; Resistance: 0-50 MΩ | Measurement of supply voltage, sensor/thermostat resistance, electric motor current. |
| Thermal imager | Resolution ≥160x120 pixels, sensitivity ≤0.1°C (for example, Flir E6) | -20°C to +350°C | Detection of local overheating, evaluation of cooler efficiency, monitoring of temperature distribution. |
| Contact thermometer (pyrometer) | Digital with K-type thermocouple (e.g. Testo 905-T2) | -50°C to +300°C | Accurate measurement of the temperature of the pipelines, the oil separator tank, and the housing. |
| Manometer (for air/oil) | Accuracy class 1.0 or higher, diameter 63 mm | 0-16 bar (air); 0-25 bar (lubricant) | Pressure measurement in the lubrication system, filters, cooler and injection line. |
| Tachometer (non-contact) | With laser pointer (e.g. PCE-DT 62) | 10-99999 rpm | Checking the rotation speed of the cooling fan. |
| Air flow meter/anemometer | Impeller or thermal (e.g. Testo 417) | 0.3-20 m/s | Evaluation of air flow through the cooler. |
4. Initial Evaluation List
Before starting a detailed diagnosis, perform the following check:
| Check/Action | Expected Result/Value | Record |
|---|---|---|
| Visual inspection of the compressor | Absence of visible oil leaks, damage to pipelines, contamination on radiators. | Mark all deviations. |
| Checking the oil level (pointer/dipstick) | The oil level is between the minimum and maximum marks during operation and after stopping. | Record the current level. |
| Record indicators from the control panel | Injection pressure (bar), injection temperature (°C), working hours (motor hours), motor current (A). | Record all current values. |
| Checking the history of accidents/alarms | To determine the frequency and nature of previous overheating trips. | Write down the error codes and the time of their occurrence. |
| Environmental conditions | Air temperature in the room (°C), availability of sufficient ventilation, absence of heat sources nearby. | Record the ambient temperature, assess ventilation. |
| Date of last service | When was the last time you changed the oil, oil filter, air filter, or cleaned the cooler. | Write down dates and work done. |
5. Systematic Diagnostic Algorithm
This algorithm will help to consistently determine the root cause of high injection temperature:
- SYMPTOM: High Discharge Temperature (> 95°C / Trip Trip)
- Oil Level Check:
- ACTION: Visually check the oil level on the dipstick or dipstick on the oil separator tank while the compressor is running and 2 minutes after stopping (while the system is not depressurized).
- IF THE RESULT: The oil level is below the minimum mark.
- PROBABLE CAUSE: Low oil level.
- GO TO: Section 7.1 Root Cause Analysis: Low Lubricant.
- IF THE RESULT: The oil level is normal.
- GO TO: Item 1.2 "Oil and Air Cooler Inspection".
- Oil and Air Cooler Inspection:
- ACTION: Visually inspect the outer surfaces of the oil and air cooler for contamination (dust, dirt, lint). Use a thermal imager to measure the temperature difference at the inlet and outlet of the cooler.
- IF THE RESULT: The external surfaces are dirty, the thermal imager shows an uneven temperature distribution or insufficient temperature drop at the cooler outlet (for example, < 10°C). An increased pressure drop across the cooler (over 0.5 bar) is also possible.
- PROBABLE CAUSE: Cooler contamination (external or internal).
- GO TO: Section 7.2 Root Cause Analysis: Oil Cooler/Air Contamination.
- IF THE RESULT: The cooler is clean, the temperature difference is normal.
- GO TO: Section 1.3 "Checking the Cooling Fan".
- Checking the Cooling Fan:
- ACTION: Visually check the operation of the cooling fan (rotation, absence of extraneous noises). Using a tachometer, measure the speed of rotation of the blades. Check the electrical connections and supply voltage to the fan motor with a multimeter.
- IF THE RESULT: The fan does not spin, spins slowly, has damaged blades, or no voltage to the motor.
- PROBABLE CAUSE: Failure of the cooling fan or its drive.
- GO TO: Section 7.5 Root Cause Analysis: Defective Cooling Fan.
- IF THE RESULT: The fan is working correctly, the rotation speed and voltage are normal.
- GO TO: Item 1.4 "Checking the Oil Thermostat".
- Checking the Oil Thermostat:
- ACTION: Measure the oil temperature before and after the thermostat with a contact thermometer. (CAUTION: Hot grease!). Some thermostats can be tested for resistance (with the power off) or disassembled for testing in hot water (according to the manufacturer's instructions).
- IF THE RESULT: The temperature of the oil after the thermostat is significantly higher or almost the same as the temperature before it, indicating that the thermostat is not opening fully or is stuck in the closed position. Or if it is stuck in the open position, the compressor takes a long time to reach operating temperature.
- PROBABLE CAUSE: Malfunction of the oil thermostat.
- GO TO: Section 7.3 Root Cause Analysis: Oil Thermostat Malfunction.
- IF THE RESULT: The thermostat is working correctly, directing the oil to cool down when the operating temperature is reached.
- GO TO: Clause 1.5 "Analysis of Environmental Conditions".
- Oil Level Check:
- Analysis of Ambient Conditions:
- ACTION: Measure the temperature of the ambient air at the point of intake by the compressor. Check the presence of obstacles to air circulation around the compressor, the efficiency of the exhaust ventilation of the room.
- IF RESULT: Ambient air temperature exceeds permissible values (usually > 35°C) or room ventilation is insufficient for heat removal.
- PROBABLE CAUSE: High ambient temperature or poor ventilation.
- GO TO: Section 7.4 Root Cause Analysis: High Environmental Conditions.
- IF RESULT: Environmental conditions are normal.
- GO TO: Item 1.6 "Oil Filter and Lubricant Type Check".
- Checking the Oil Filter and Lubricant Type:
- ACTION: Check the pressure drop reading on the oil filter (if equipped). Estimate the date of the last oil and filter change. Be sure to use the correct type and viscosity of oil recommended by the compressor manufacturer. Take a sample of the lubricant for analysis if degradation is suspected.
- IF THE RESULT: Increased pressure drop on the oil filter (> 0.5 bar), the lubricant has not been changed for a long time, or the wrong type of lubricant is used.
- PROBABLE CAUSE: Clogged oil filter or degraded/incorrect oil.
- GO TO: Section 7.6 Root Cause Analysis: Clogged Oil Filter / Degraded Oil.
- IF RESULT: All previous checks found no cause.
- PROBABLE CAUSE: Other, less common causes are possible (non-return valve failure, wear of screw unit elements, compressor overload). In-depth diagnosis or referral to specialists is required.
6. Matrix "Symptom - Probable Causes"
| Symptom | Probable Causes (ranked by likelihood) | Diagnostic Test | Expected Result if Cause Confirmed |
|---|---|---|---|
| High injection temperature |
|
|
|
7. Root Cause Analysis for Each Malfunction
7.1. Low Lubricant Level
Explanation: The oil in a screw compressor performs several critical functions: lubrication, cooling, and sealing. An insufficient level of lubricant leads to a decrease in its circulation and cooling efficiency. This causes an increase in temperature in the screw unit due to increased friction and insufficient heat dissipation.
How to confirm: Visual inspection of the oil level indicator (as a rule, during the operation of the compressor, the level should be within the MIN and MAX marks, or by the dipstick after the pressure has stabilized). If the level is below the minimum mark by 1/3 of the volume or more, this is a confirmation.
Consequences, if not eliminated: Insufficient lubrication will lead to accelerated wear of bearings, seals and rotor profiles, increased clearances, increased energy consumption, and ultimately - to jamming of the screw block, which is the most expensive element of the compressor.
7.2. Oil Cooler and Air Contamination
Explanation: Cooler radiators (oil and air) are designed to remove heat from the oil and compressed air to the environment. External contamination (dust, dirt, lint) reduces the heat exchange surface area, preventing effective heat transfer. Internal contamination (oil sludge, scale from hard water in water-cooled compressors) creates an insulating layer that also reduces cooling efficiency.
How to confirm:
- External: A layer of dust or dirt is visually visible on the radiator fins. The thermal imager will show areas with a higher temperature on the surface of the cooler, where contamination is the densest, as well as insufficient temperature difference of the air passing through the radiator.
- Internal: After external cleaning, the problem persists. Measuring the oil pressure drop across the cooler (ΔP > 0.5 bar) may indicate internal deposits.
Consequences, if not eliminated: Constant overheating of the lubricant leads to its rapid degradation (oxidation, loss of viscosity), the formation of varnishes and deposits that can clog the oil lines and the oil separator. The overall efficiency of the compressor decreases, electricity consumption increases, and the service life of components shortens.
7.3. Malfunction of the Oil Thermostat
Explanation: The oil thermostat regulates the flow of oil through the cooler, maintaining its temperature in the optimal range. If the thermostat is stuck in the closed position, the oil does not enter the cooler or does not get into it in sufficient quantity, which leads to its overheating. If the thermostat is stuck in the fully open position, the compressor may be operating at too low a temperature, which is a less common cause of overheating, but can cause excessive water condensation in the oil and oil degradation.
How to confirm:
- Stick in closed position: Measure the oil temperature before and after the thermostat with a contact thermometer. If the temperature to the cooler is much higher than the operating temperature, and the temperature after the thermostat does not decrease properly, this indicates its malfunction.
- Checking resistance: If it's an electric thermostat, check its resistance with a multimeter.
Consequences, if not eliminated: Permanent overheating of the lubricant and its rapid degradation, as described above. Increase in the amount of condensate in the system when jammed in the open position.
7.4. High Environmental Conditions / Poor Ventilation
Explanation: Screw compressors are designed to operate in a certain range of ambient temperatures (usually from +5°C to +40°C according to ISO 1217). If the temperature of the air entering the compressor for cooling is too high (eg > 35°C), or if the room is not well ventilated, the efficiency of the chillers is significantly reduced. This leads to an increase in the operating temperature of the lubricant and injection air.
How to confirm: Measure the temperature of the air at the intake point of the compressor and around it with a thermometer. Check the operation of the supply and exhaust ventilation, the absence of obstacles to the air flow, the correct placement of the compressor and other heat sources. Estimate the volume of air passing through the vents using an anemometer.
Consequences, if not eliminated: Overheating of the compressor, frequent shutdowns due to temperature, shortening the service life of components, increased energy consumption due to inefficient operation.
7.5. Defective cooling fan
Explanation: The cooling fan is responsible for ensuring the necessary air flow through the radiators of the coolers. Failure of the fan motor, broken drive belt, damage to the blades or clogging of the protective grid lead to a decrease in the volume of air passing through the coolers and, as a result, to an increase in temperature.
How to confirm:
- Visual inspection: Check the integrity of the fan blades, the presence of a belt (for belt drives), the absence of foreign objects that prevent rotation.
- Rotation: Make sure the fan rotates when the compressor is running.
- Rotation speed: Measure the rotation speed with a tachometer. Compare with passport data.
- Electrical check: Using a multimeter, check the supply voltage and current consumption of the fan motor. A faulty motor may have abnormal current or no voltage.
Consequences if not eliminated: Insufficient cooling, similar to the contamination of coolers, with all the resulting consequences for the lubrication and life of the compressor.
7.6. Clogged Oil Filter / Degraded Oil
Explanation: The oil filter removes contaminants from the oil, protecting the compressor components. A clogged filter creates excessive resistance to oil flow, reducing oil circulation and cooling efficiency. This can cause the filter bypass valve to open, allowing raw oil to circulate through the system. Degraded lubricant (oxidized, with lost viscosity) loses its lubrication and heat dissipation properties, contributing to overheating.
How to confirm:
- Pressure drop: High pressure drop across the oil filter (> 0.5 bar) if the compressor is equipped with appropriate sensors.
- Filter/lubricant age: Check date of last change.
- Visual assessment of lubricant: Color change (darker than normal), appearance of sediment, specific smell.
- Lubricant analysis: Laboratory analysis will confirm degradation, the presence of water, metal particles and changes in viscosity.
Consequences if not eliminated: Accelerated wear of moving parts, damage to bearings and screw unit due to dirty or ineffective lubrication. Reducing the service life of the oil separator.
8. Step-by-step Removal Procedures
Make sure all precautions in Section 2 are followed before performing any procedures.
8.1. Eliminating Low Lubricant Level
SAFETY CHECK: Apply LOTO, depressurize the system.
- Determine the cause of the low oil level (leakage, entrainment). Repair the leak, if any.
- Fill in new compressor oil recommended by the manufacturer (UNITEC offers a wide range of compatible oils). The volume of lubricant should be up to the MAX mark on the level indicator.
- Start the compressor, let it work for 5-10 minutes, then stop.
- Check the oil level 2 minutes after stopping (before depressurization). If necessary, top up to the optimal level.
- VERIFICATION: Monitoring of discharge temperature after start-up. It should stabilize in the standard range (70-95°C).
8.2. Oil and Air Cooler Cleaning/Flushing
SAFETY CHECK: Apply LOTO, depressurize system, allow cooler to cool.
- External cleaning: Using compressed air (maximum 2-3 bar), blow the cooler fins from the opposite direction of the air flow. Use a soft brush or vacuum cleaner to remove stubborn dirt.
CAUTION: Do not damage the lamellae!
- Internal cleaning (for heavily contaminated): If external cleaning did not help, the cooler must be dismantled. Flush it with a special oil system cleaning solution or chemical descaling agent (for water coolers) according to the manufacturer's instructions. Rinse with clean water, then blow dry.
- Install the cooler in place, check all connections for tightness.
- VERIFICATION: After starting the compressor, monitor the discharge temperature and the temperature drop on the cooler using a thermal imager or a contact thermometer. The air temperature drop through the radiator should be at least 10°C, and the discharge temperature should be within the normal range.
8.3. Replacing a Defective Oil Thermostat
SAFETY CHECK: Apply LOTO, depressurize system, allow to cool.
- Drain the oil from the compressor (or part if the thermostat is high).
- Disconnect the pipes from the thermostat.
- Disassemble the faulty thermostat.
- Install a new thermostat (UNITEC offers original spare parts and quality analogues), make sure the orientation is correct (flow arrows). Tighten the connection according to the tightening torque specified in the manual (usually 30-50 Nm).
- Fill in the oil, check the level.
- VERIFICATION: Start the compressor. Monitor the oil temperature. It should gradually increase to the working range, and then stabilize, which indicates the correct operation of the thermostat.
8.4. Optimization of Environmental Conditions
SAFETY CHECK: General safety rules must be observed when working near the compressor.
- Measure the temperature of the surrounding air. If it exceeds 35°C, measures must be taken to reduce the temperature in the room or to ensure that cold air is supplied to the compressor.
- Check the efficiency of supply and exhaust ventilation. Make sure the exhaust fans are running and the intake vents are not blocked. The volume of exhaust air should be 10-15% greater than the volume of supply air to create a small rarefaction.
- Remove any obstructions to the free flow of air around the compressor (minimum recommended clearance from walls: 1 meter).
- Make sure that the hot air drawn from the compressor does not recirculate back to the compressor intake.
- VERIFICATION: Repeated measurement of the ambient air temperature, which should be within the permissible values. Compressor discharge temperature monitoring.
8.5. Repair/Replacement of Cooling Fan
SECURITY CHECK: Apply LOTO, let cool. Beware of moving parts.
- Visual inspection: Check the fan blades for damage.
- Checking the drive: For belt drives - check the tension and condition of the belt. For direct drives — check for foreign objects.
- Electrical check: Using a multimeter, check the supply voltage to the fan motor. If there is voltage and the motor does not turn, check the windings for an open or short circuit.
- Replace the faulty motor, belt, or fan blades. Install components that meet OEM specifications.
- VERIFICATION: Start the compressor, make sure the fan is rotating at the correct speed (use a tachometer). Check the discharge temperature.
8.6. Replacing the Oil Filter and/or Lubricant
SAFETY CHECK: Apply LOTO, depressurize system, allow to cool.
- Drain all old oil from the compressor.
- Remove the old oil filter.
- Install a new original or certified analogue UNITEC oil filter. Apply a thin layer of new oil to the filter O-ring, hand tighten, then tighten 3/4 or 1 turn according to the manufacturer's instructions.
- Fill in new compressor oil recommended by the manufacturer of the appropriate viscosity grade (eg ISO VG 46 or VG 68). The volume of lubricant should be up to the MAX mark.
- Run the compressor for a short time (1-2 minutes), then stop.
- Check the oil level and the absence of leaks. Top up if necessary.
- VERIFICATION: Injection temperature monitoring. It should return to normal.
9. Preventive Measures
Regular maintenance is key to preventing high discharge temperatures and ensuring compressor longevity.
| The root cause | Prevention Strategy | Monitoring method | Recommended Interval |
|---|---|---|---|
| Low oil level | Regular checking of the oil level and topping up. Elimination of leaks. | Visual inspection of the level indicator/dipstick. | Daily/Weekly. |
| Contamination of the cooler | Scheduled external cleaning of coolers. | Visual inspection, thermal imaging control, pressure drop control. | Monthly/Quarterly (depends on conditions). |
| Thermostat malfunction | Scheduled check of the functionality of the thermostat (if provided by the manufacturer). | Temperature measurement before/after the thermostat. | Once a year or at each scheduled maintenance. |
| High environmental conditions / Poor ventilation | Maintenance of proper ventilation of the room, temperature monitoring. | Measurement of room temperature, inspection of ventilation systems. | Daily/Monthly. |
| Defective cooling fan | Regular inspection of the fan, checking of the electrical parameters of the motor. | Visual inspection, rotation speed control, motor current measurement. | Monthly/Quarterly. |
| Clogged oil filter / Degraded lubricant | Timely replacement of the oil filter and lubricant in accordance with the manufacturer's regulations. Using the recommended lubricant. | Control of run-in, visual evaluation of lubricant, control of pressure drop on the filter. | According to the manufacturer's regulations (usually 2000-4000 hours or 1 year). |
10. Spare Parts and Components
For quick and efficient troubleshooting, it is recommended to have the following spare parts in stock. UNITEC-D GmbH offers a wide range of high-quality components for screw compressors, certified by CE and UkrSEPRO.
| Description of the Part | Specification | When to Replace | Category UNITEC |
|---|---|---|---|
| Compressor oil | As per OEM recommendations (ISO VG 46, VG 68, Synthetic/Mineral) | According to the regulations (2000-8000 hours) or during degradation | Lubricants and Technical Fluids |
| Oil filter | Original OEM number or certified equivalent | According to the regulations (2000-4000 hours) or with increased ΔP | Filters |
| Air filter | Original OEM number or certified equivalent | According to the regulations (1000-4000 hours) or with increased ΔP | Filters |
| Oil thermostat | Opening temperature, original OEM number | In the event of a malfunction (spell, incorrect operation) | Valves and Control Elements |
| Cooling fan (motor/impeller) | Power, voltage, size, original OEM number | In the event of a malfunction or significant wear and tear | Electric motors and drives |
| Drive belt (if equipped) | Type, length, profile (eg SPB, A) | With wear, cracks, stretching | Belt Transmissions |
| Oil separator | Original OEM number or certified equivalent | According to the regulations (4000-8000 hours) | Filters |
| Temperature sensor | Type (PT100, NTC), range, original OEM number | In case of incorrect readings | Sensors and Automation |
For ordering and detailed spare parts catalog visit: www.unitecd.com/e-catalog/
11. Links
- DSTU ISO 1217:2018 (ISO 1217:2009, IDT) Volumetric compressors. Admission test.
- DSTU EN 1037:2018 (EN 1037:1995, IDT) Machine safety. Prevention of unexpected start.
- Compressor manufacturer (OEM) operation and maintenance manuals.
- Relevant standards of the ISO 4406 series (purity of hydraulic fluids), ISO 2909 (determination of the viscosity index of lubricants).
- UNITEC-D GmbH: Manuals for maintenance of pneumatic systems.